GovSteamSGO
Class Description
Simplified steam turbine governor.
Attributes
Name | Type | Description |
---|---|---|
k1 | PU | One / PU regulation (<i>K1</i>). |
k2 | PU | Fraction (<i>K2</i>). |
k3 | PU | Fraction (<i>K3</i>). |
mwbase | ActivePower | Base for power values (<i>MWbase</i>) (> 0). Unit = MW. |
pmax | PU | Upper power limit (<i>Pmax</i>) (> GovSteamSGO.pmin). |
pmin | Seconds | Lower power limit (<i>Pmin</i>) (>= 0 and < GovSteamSGO.pmax). |
t1 | Seconds | Controller lag (<i>T1</i>) (>= 0). |
t2 | Seconds | Controller lead compensation (<i>T2</i>) (>= 0). |
t3 | Seconds | Governor lag (<i>T3</i>) (> 0). |
t4 | Seconds | Delay due to steam inlet volumes associated with steam chest and inlet piping (<i>T4</i>) (>= 0). |
t5 | Seconds | Reheater delay including hot and cold leads (<i>T5</i>) (>= 0). |
t6 | Seconds | Delay due to IP-LP turbine, crossover pipes and LP end hoods (<i>T6</i>) (>= 0). |
Relationships
Ancestors
Descendents
No descendent classes
Associations
None