Class Description

IEEE simplified hydro governor-turbine model. Used for mechanical-hydraulic and electro-hydraulic turbine governors, with or without steam feedback. Typical values given are for mechanical-hydraulic turbine-governor. Ref<font color="#0f0f0f">erence: IEEE Transactions on Power Apparatus and Systems, November/December 1973, Volume PAS-92, Number 6, <i><u>Dynamic Models for Steam and Hydro Turbines in Power System Studies</u></i>, page 1904.</font>

Attributes

NameTypeDescription
kPUGovernor gain (<i>K)</i>.
mwbaseActivePowerBase for power values (<i>MWbase</i>) (> 0). Unit = MW.
pmaxPUGate maximum (<i>Pmax</i>) (> GovHydroIEEE0.pmin).
pminPUGate minimum (<i>Pmin</i>) (< GovHydroIEEE.pmax).
t1SecondsGovernor lag time constant (<i>T1</i>) (>= 0). Typical value = 0,25.
t2SecondsGovernor lead time constant (<i>T2)</i> (>= 0). Typical value = 0.
t3SecondsGate actuator time constant (<i>T3</i>) (>= 0). Typical value = 0,1.
t4SecondsWater starting time (<i>T4</i>) (>= 0).

Relationships

Ancestors

Descendents

No descendent classes

Associations