GovHydroIEEE0
Class Description
IEEE simplified hydro governor-turbine model. Used for mechanical-hydraulic and electro-hydraulic turbine governors, with or without steam feedback. Typical values given are for mechanical-hydraulic turbine-governor. Ref<font color="#0f0f0f">erence: IEEE Transactions on Power Apparatus and Systems, November/December 1973, Volume PAS-92, Number 6, <i><u>Dynamic Models for Steam and Hydro Turbines in Power System Studies</u></i>, page 1904.</font>
Attributes
Name | Type | Description |
---|---|---|
k | PU | Governor gain (<i>K)</i>. |
mwbase | ActivePower | Base for power values (<i>MWbase</i>) (> 0). Unit = MW. |
pmax | PU | Gate maximum (<i>Pmax</i>) (> GovHydroIEEE0.pmin). |
pmin | PU | Gate minimum (<i>Pmin</i>) (< GovHydroIEEE.pmax). |
t1 | Seconds | Governor lag time constant (<i>T1</i>) (>= 0). Typical value = 0,25. |
t2 | Seconds | Governor lead time constant (<i>T2)</i> (>= 0). Typical value = 0. |
t3 | Seconds | Gate actuator time constant (<i>T3</i>) (>= 0). Typical value = 0,1. |
t4 | Seconds | Water starting time (<i>T4</i>) (>= 0). |
Relationships
Ancestors
Descendents
No descendent classes
Associations
None