GovSteamCC
Class Description
Cross compound turbine governor. Unlike tandem compound units, cross compound units are not on the same shaft.
Attributes
Name | Type | Description |
---|---|---|
dhp | PU | HP damping factor (<i>Dhp</i>). Typical value = 0. |
dlp | PU | LP damping factor (<i>Dlp</i>). Typical value = 0. |
fhp | PU | Fraction of HP power ahead of reheater (<i>Fhp</i>). Typical value = 0,3. |
flp | PU | Fraction of LP power ahead of reheater (<i>Flp</i>). Typical value = 0,7. |
mwbase | ActivePower | Base for power values (<i>MWbase</i>) (> 0). Unit = MW. |
pmaxhp | PU | Maximum HP value position (<i>Pmaxhp</i>). Typical value = 1. |
pmaxlp | PU | Maximum LP value position (<i>Pmaxlp</i>). Typical value = 1. |
rhp | PU | HP governor droop (<i>Rhp</i>) (> 0). Typical value = 0,05. |
rlp | PU | LP governor droop (<i>Rlp</i>) (> 0). Typical value = 0,05. |
t1hp | Seconds | HP governor time constant (<i>T1hp</i>) (>= 0). Typical value = 0,1. |
t1lp | Seconds | LP governor time constant (<i>T1lp</i>) (>= 0). Typical value = 0,1. |
t3hp | Seconds | HP turbine time constant (<i>T3hp</i>) (>= 0). Typical value = 0,1. |
t3lp | Seconds | LP turbine time constant (<i>T3lp</i>) (>= 0). Typical value = 0,1. |
t4hp | Seconds | HP turbine time constant (<i>T4hp</i>) (>= 0). Typical value = 0,1. |
t4lp | Seconds | LP turbine time constant (<i>T4lp</i>) (>= 0). Typical value = 0,1. |
t5hp | Seconds | HP reheater time constant (<i>T5hp</i>) (>= 0). Typical value = 10. |
t5lp | Seconds | LP reheater time constant (<i>T5lp</i>) (>= 0). Typical value = 10. |
Relationships
Ancestors
Descendents
No descendent classes
Associations
None