GovSteam1
Class Description
Steam turbine governor, based on the GovSteamIEEE1 (with optional deadband and nonlinear valve gain added).
Attributes
Name | Type | Description |
---|---|---|
db1 | Frequency | Intentional deadband width (<i>db1</i>). Unit = Hz. Typical value = 0. |
db2 | ActivePower | Unintentional deadband (<i>db2</i>). Unit = MW. Typical value = 0. |
eps | Frequency | Intentional db hysteresis (<i>eps</i>). Unit = Hz. Typical value = 0. |
gv1 | PU | Nonlinear gain valve position point 1 (<i>GV1</i>). Typical value = 0. |
gv2 | PU | Nonlinear gain valve position point 2 (<i>GV2</i>). Typical value = 0,4. |
gv3 | PU | Nonlinear gain valve position point 3 (<i>GV3</i>). Typical value = 0,5. |
gv4 | PU | Nonlinear gain valve position point 4 (<i>GV4</i>). Typical value = 0,6. |
gv5 | PU | Nonlinear gain valve position point 5 (<i>GV5</i>). Typical value = 1. |
gv6 | PU | Nonlinear gain valve position point 6 (<i>GV6</i>). Typical value = 0. |
k | PU | Governor gain (reciprocal of droop) (<i>K</i>) (> 0). Typical value = 25. |
k1 | Float | Fraction of HP shaft power after first boiler pass (<i>K1</i>). Typical value = 0,2. |
k2 | Float | Fraction of LP shaft power after first boiler pass (<i>K2</i>). Typical value = 0. |
k3 | Float | Fraction of HP shaft power after second boiler pass (<i>K3</i>). Typical value = 0,3. |
k4 | Float | Fraction of LP shaft power after second boiler pass (<i>K4</i>). Typical value = 0. |
k5 | Float | Fraction of HP shaft power after third boiler pass (<i>K5</i>). Typical value = 0,5. |
k6 | Float | Fraction of LP shaft power after third boiler pass (<i>K6</i>). Typical value = 0. |
k7 | Float | Fraction of HP shaft power after fourth boiler pass (<i>K7</i>). Typical value = 0. |
k8 | Float | Fraction of LP shaft power after fourth boiler pass (<i>K8</i>). Typical value = 0. |
mwbase | ActivePower | Base for power values (<i>MWbase</i>) (> 0). Unit = MW. |
pgv1 | PU | Nonlinear gain power value point 1 (<i>Pgv1</i>). Typical value = 0. |
pgv2 | PU | Nonlinear gain power value point 2 (<i>Pgv2</i>). Typical value = 0,75. |
pgv3 | PU | Nonlinear gain power value point 3 (<i>Pgv3</i>). Typical value = 0,91. |
pgv4 | PU | Nonlinear gain power value point 4 (<i>Pgv4</i>). Typical value = 0,98. |
pgv5 | PU | Nonlinear gain power value point 5 (<i>Pgv5</i>). Typical value = 1. |
pgv6 | PU | Nonlinear gain power value point 6 (<i>Pgv6</i>). Typical value = 0. |
pmax | PU | Maximum valve opening (<i>Pmax</i>) (> GovSteam1.pmin). Typical value = 1. |
pmin | PU | Minimum valve opening (<i>Pmin</i>) (>= 0 and < GovSteam1.pmax). Typical value = 0. |
sdb1 | Boolean | Intentional deadband indicator. true = intentional deadband is applied false = intentional deadband is not applied. Typical value = true. |
sdb2 | Boolean | Unintentional deadband location. true = intentional deadband is applied before point "A" false = intentional deadband is applied after point "A". Typical value = true. |
t1 | Seconds | Governor lag time constant (<i>T1</i>) (>= 0). Typical value = 0. |
t2 | Seconds | Governor lead time constant (<i>T2</i>) (>= 0). Typical value = 0. |
t3 | Seconds | Valve positioner time constant (<i>T3) </i>(> 0). Typical value = 0,1. |
t4 | Seconds | Inlet piping/steam bowl time constant (<i>T4</i>) (>= 0). Typical value = 0,3. |
t5 | Seconds | Time constant of second boiler pass (<i>T5</i>) (>= 0). Typical value = 5. |
t6 | Seconds | Time constant of third boiler pass (<i>T6</i>) (>= 0). Typical value = 0,5. |
t7 | Seconds | Time constant of fourth boiler pass (<i>T7</i>) (>= 0). Typical value = 0. |
uc | Float | Maximum valve closing velocity (<i>Uc</i>) (< 0). Unit = PU / s. Typical value = -10. |
uo | Float | Maximum valve opening velocity (<i>Uo</i>) (> 0). Unit = PU / s. Typical value = 1. |
valve | Boolean | Nonlinear valve characteristic. true = nonlinear valve characteristic is used false = nonlinear valve characteristic is not used. Typical value = true. |