GovSteam1

Class Description

Steam turbine governor, based on the GovSteamIEEE1 (with optional deadband and nonlinear valve gain added).

Attributes

NameTypeDescription
db1FrequencyIntentional deadband width (<i>db1</i>). Unit = Hz. Typical value = 0.
db2ActivePowerUnintentional deadband (<i>db2</i>). Unit = MW. Typical value = 0.
epsFrequencyIntentional db hysteresis (<i>eps</i>). Unit = Hz. Typical value = 0.
gv1PUNonlinear gain valve position point 1 (<i>GV1</i>). Typical value = 0.
gv2PUNonlinear gain valve position point 2 (<i>GV2</i>). Typical value = 0,4.
gv3PUNonlinear gain valve position point 3 (<i>GV3</i>). Typical value = 0,5.
gv4PUNonlinear gain valve position point 4 (<i>GV4</i>). Typical value = 0,6.
gv5PUNonlinear gain valve position point 5 (<i>GV5</i>). Typical value = 1.
gv6PUNonlinear gain valve position point 6 (<i>GV6</i>). Typical value = 0.
kPUGovernor gain (reciprocal of droop) (<i>K</i>) (> 0). Typical value = 25.
k1FloatFraction of HP shaft power after first boiler pass (<i>K1</i>). Typical value = 0,2.
k2FloatFraction of LP shaft power after first boiler pass (<i>K2</i>). Typical value = 0.
k3FloatFraction of HP shaft power after second boiler pass (<i>K3</i>). Typical value = 0,3.
k4FloatFraction of LP shaft power after second boiler pass (<i>K4</i>). Typical value = 0.
k5FloatFraction of HP shaft power after third boiler pass (<i>K5</i>). Typical value = 0,5.
k6FloatFraction of LP shaft power after third boiler pass (<i>K6</i>). Typical value = 0.
k7FloatFraction of HP shaft power after fourth boiler pass (<i>K7</i>). Typical value = 0.
k8FloatFraction of LP shaft power after fourth boiler pass (<i>K8</i>). Typical value = 0.
mwbaseActivePowerBase for power values (<i>MWbase</i>) (> 0). Unit = MW.
pgv1PUNonlinear gain power value point 1 (<i>Pgv1</i>). Typical value = 0.
pgv2PUNonlinear gain power value point 2 (<i>Pgv2</i>). Typical value = 0,75.
pgv3PUNonlinear gain power value point 3 (<i>Pgv3</i>). Typical value = 0,91.
pgv4PUNonlinear gain power value point 4 (<i>Pgv4</i>). Typical value = 0,98.
pgv5PUNonlinear gain power value point 5 (<i>Pgv5</i>). Typical value = 1.
pgv6PUNonlinear gain power value point 6 (<i>Pgv6</i>). Typical value = 0.
pmaxPUMaximum valve opening (<i>Pmax</i>) (> GovSteam1.pmin). Typical value = 1.
pminPUMinimum valve opening (<i>Pmin</i>) (>= 0 and < GovSteam1.pmax). Typical value = 0.
sdb1BooleanIntentional deadband indicator.
true = intentional deadband is applied
false = intentional deadband is not applied.
Typical value = true.
sdb2BooleanUnintentional deadband location.
true = intentional deadband is applied before point "A"
false = intentional deadband is applied after point "A".
Typical value = true.
t1SecondsGovernor lag time constant (<i>T1</i>) (>= 0). Typical value = 0.
t2SecondsGovernor lead time constant (<i>T2</i>) (>= 0). Typical value = 0.
t3SecondsValve positioner time constant (<i>T3) </i>(> 0). Typical value = 0,1.
t4SecondsInlet piping/steam bowl time constant (<i>T4</i>) (>= 0). Typical value = 0,3.
t5SecondsTime constant of second boiler pass (<i>T5</i>) (>= 0). Typical value = 5.
t6SecondsTime constant of third boiler pass (<i>T6</i>) (>= 0). Typical value = 0,5.
t7SecondsTime constant of fourth boiler pass (<i>T7</i>) (>= 0). Typical value = 0.
ucFloatMaximum valve closing velocity (<i>Uc</i>) (< 0). Unit = PU / s. Typical value = -10.
uoFloatMaximum valve opening velocity (<i>Uo</i>) (> 0). Unit = PU / s. Typical value = 1.
valveBooleanNonlinear valve characteristic.
true = nonlinear valve characteristic is used
false = nonlinear valve characteristic is not used.
Typical value = true.