GovSteamFV3

Class Description

Simplified GovSteamIEEE1 steam turbine governor with Prmax limit and fast valving.

Attributes

NameTypeDescription
gv1PUNonlinear gain valve position point 1 (<i>GV1</i>). Typical value = 0.
gv2PUNonlinear gain valve position point 2 (<i>GV2</i>). Typical value = 0,4.
gv3PUNonlinear gain valve position point 3 (<i>GV3</i>). Typical value = 0,5.
gv4PUNonlinear gain valve position point 4 (<i>GV4</i>). Typical value = 0,6.
gv5PUNonlinear gain valve position point 5 (<i>GV5</i>). Typical value = 1.
gv6PUNonlinear gain valve position point 6 (<i>GV6</i>). Typical value = 0.
kPUGovernor gain, (reciprocal of droop) (<i>K</i>). Typical value = 20.
k1PUFraction of turbine power developed after first boiler pass (<i>K1</i>). Typical value = 0,2.
k2PUFraction of turbine power developed after second boiler pass (<i>K2</i>). Typical value = 0,2.
k3PUFraction of hp turbine power developed after crossover or third boiler pass (<i>K3</i>). Typical value = 0,6.
mwbaseActivePowerBase for power values (<i>MWbase</i>) (> 0). Unit = MW.
pgv1PUNonlinear gain power value point 1 (<i>Pgv1</i>). Typical value = 0.
pgv2PUNonlinear gain power value point 2 (<i>Pgv2</i>). Typical value = 0,75.
pgv3PUNonlinear gain power value point 3 (<i>Pgv3</i>). Typical value = 0,91.
pgv4PUNonlinear gain power value point 4 (<i>Pgv4</i>). Typical value = 0,98.
pgv5PUNonlinear gain power value point 5 (<i>Pgv5</i>). Typical value = 1.
pgv6PUNonlinear gain power value point 6 (<i>Pgv6</i>). Typical value = 0.
pmaxPUMaximum valve opening, PU of <i>MWbase</i> (<i>Pmax</i>) (> GovSteamFV3.pmin). Typical value = 1.
pminPUMinimum valve opening, PU of <i>MWbase</i> (<i>Pmin</i>) (< GovSteamFV3.pmax). Typical value = 0.
prmaxPUMax. pressure in reheater (<i>Prmax</i>). Typical value = 1.
t1SecondsGovernor lead time constant (<i>T1</i>) (>= 0). Typical value = 0.
t2SecondsGovernor lag time constant (<i>T2</i>) (>= 0). Typical value = 0.
t3SecondsValve positioner time constant (<i>T3</i>) (> 0). Typical value = 0.
t4SecondsInlet piping/steam bowl time constant (<i>T4</i>) (>= 0). Typical value = 0,2.
t5SecondsTime constant of second boiler pass (i.e. reheater) (<i>T5</i>) (> 0 if fast valving is used, otherwise >= 0). Typical value = 0,5.
t6SecondsTime constant of crossover or third boiler pass (<i>T6</i>) (>= 0). Typical value = 10.
taSecondsTime to close intercept valve (IV) (<i>Ta</i>) (>= 0). Typical value = 0,97.
tbSecondsTime until IV starts to reopen (<i>Tb</i>) (>= 0). Typical value = 0,98.
tcSecondsTime until IV is fully open (<i>Tc</i>) (>= 0). Typical value = 0,99.
ucFloatMaximum valve closing velocity (<i>Uc</i>). Unit = PU / s. Typical value = -1.
uoFloatMaximum valve opening velocity (<i>Uo</i>). Unit = PU / s. Typical value = 0,1.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None