Skip to main content

GovHydroWEH

Class Description

Woodward<sup>TM </sup>electric hydro governor. [Footnote: Woodward electric hydro governors are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]

Attributes

NameTypeDescription
dbPUSpeed deadband (<i>db</i>).
dicnPUValue to allow the integral controller to advance beyond the gate limits (<i>Dicn</i>).
dpvPUValue to allow the pilot valve controller to advance beyond the gate limits (<i>Dpv</i>).
dturbPUTurbine damping factor (<i>Dturb</i>). Unit = delta P (PU of <i>MWbase</i>) / delta speed (PU).
feedbackSignalBooleanFeedback signal selection (<i>Sw</i>).
true = PID output (if <i>R-Perm-Gate </i>= droop and <i>R-Perm-Pe </i>= 0)
false = electrical power (if <i>R-Perm-Gate </i>= 0 and <i>R-Perm-Pe </i>= droop) or
false = gate position (if R<i>-Perm-Gate </i>= droop and <i>R-Perm-Pe </i>= 0).
Typical value = false.
fl1PUFlowgate 1 (<i>Fl1</i>). Flow value for gate position point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
fl2PUFlowgate 2 (<i>Fl2</i>). Flow value for gate position point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
fl3PUFlowgate 3 (<i>Fl3</i>). Flow value for gate position point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
fl4PUFlowgate 4 (<i>Fl4</i>). Flow value for gate position point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
fl5PUFlowgate 5 (<i>Fl5</i>). Flow value for gate position point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
fp1PUFlow P1 (<i>Fp1</i>). Turbine flow value for point 1 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp10PUFlow P10 (<i>Fp10</i>). Turbine flow value for point 10 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp2PUFlow P2 (<i>Fp2</i>). Turbine flow value for point 2 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp3PUFlow P3 (<i>Fp3</i>). Turbine flow value for point 3 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp4PUFlow P4 (<i>Fp4</i>). Turbine flow value for point 4 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp5PUFlow P5 (<i>Fp5</i>). Turbine flow value for point 5 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp6PUFlow P6 (<i>Fp6</i>). Turbine flow value for point 6 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp7PUFlow P7 (<i>Fp7</i>). Turbine flow value for point 7 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp8PUFlow P8 (<i>Fp8</i>). Turbine flow value for point 8 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp9PUFlow P9 (<i>Fp9</i>). Turbine flow value for point 9 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
gmaxPUMaximum gate position (<i>Gmax</i>) (> GovHydroWEH.gmin).
gminPUMinimum gate position (<i>Gmin</i>) (< GovHydroWEH.gmax).
gtmxclPUMaximum gate closing rate (<i>Gtmxcl</i>).
gtmxopPUMaximum gate opening rate (<i>Gtmxop</i>).
gv1PUGate 1 (<i>Gv1</i>). Gate Position value for point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
gv2PUGate 2 (<i>Gv2</i>). Gate Position value for point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
gv3PUGate 3 (<i>Gv3</i>). Gate Position value for point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
gv4PUGate 4 (<i>Gv4</i>). Gate Position value for point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
gv5PUGate 5 (<i>Gv5</i>). Gate Position value for point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
kdPUDerivative controller derivative gain (<i>Kd</i>).
kiPUDerivative controller Integral gain (<i>Ki</i>).
kpPUDerivative control gain (<i>Kp</i>).
mwbaseActivePowerBase for power values (<i>MWbase</i>) (> 0). Unit = MW.
pmss1PUPmss flow P1 (<i>Pmss1</i>). Mechanical power output for turbine flow point 1 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss10PUPmss flow P10 (<i>Pmss10</i>). Mechanical power output for turbine flow point 10 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss2PUPmss flow P2 (<i>Pmss2</i>). Mechanical power output for turbine flow point 2 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss3PUPmss flow P3 (<i>Pmss3</i>). Mechanical power output for turbine flow point 3 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss4PUPmss flow P4 (<i>Pmss4</i>). Mechanical power output for turbine flow point 4 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss5PUPmss flow P5 (<i>Pmss5</i>). Mechanical power output for turbine flow point 5 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss6PUPmss flow P6 (<i>Pmss6</i>). Mechanical power output for turbine flow point 6 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss7PUPmss flow P7 (<i>Pmss7</i>). Mechanical power output for turbine flow point 7 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss8PUPmss flow P8 (<i>Pmss8</i>). Mechanical power output for turbine flow point 8 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss9PUPmss flow P9 (<i>Pmss9</i>). Mechanical power output for turbine flow point 9 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
rpgFloatPermanent droop for governor output feedback (<i>R-Perm-Gate</i>).
rppFloatPermanent droop for electrical power feedback (<i>R-Perm-Pe</i>).
tdSecondsDerivative controller time constant (<i>Td</i>) (>= 0). Limits the derivative characteristic beyond a breakdown frequency to avoid amplification of high-frequency noise.
tdvSecondsDistributive valve time lag time constant (<i>Tdv</i>) (>= 0).
tgSecondsValue to allow the distribution valve controller to advance beyond the gate movement rate limit (<i>Tg</i>) (>= 0).
tpSecondsPilot valve time lag time constant (<i>Tp</i>) (>= 0).
tpeSecondsElectrical power droop time constant (<i>Tpe</i>) (>= 0).
twSecondsWater inertia time constant (<i>Tw</i>) (> 0).

Relationships

Ancestors

Descendents

No descendent classes

Associations

None