Skip to main content

GovHydro1

Class Description

Basic hydro turbine governor.

Attributes

NameTypeDescription
atPUTurbine gain (<i>At</i>) (> 0). Typical value = 1,2.
dturbPUTurbine damping factor (<i>Dturb</i>) (>= 0). Typical value = 0,5.
gmaxPUMaximum gate opening (<i>Gmax</i>) (> 0 and > GovHydro.gmin). Typical value = 1.
gminPUMinimum gate opening (<i>Gmin</i>) (>= 0 and < GovHydro1.gmax). Typical value = 0.
hdamPUTurbine nominal head (<i>hdam</i>). Typical value = 1.
mwbaseActivePowerBase for power values (<i>MWbase</i>) (> 0). Unit = MW.
qnlPUNo-load flow at nominal head (<i>qnl</i>) (>= 0). Typical value = 0,08.
rpermPUPermanent droop (<i>R</i>) (> 0). Typical value = 0,04.
rtempPUTemporary droop (<i>r</i>) (> GovHydro1.rperm). Typical value = 0,3.
tfSecondsFilter time constant (<i>Tf</i>) (> 0). Typical value = 0,05.
tgSecondsGate servo time constant (<i>Tg</i>) (> 0). Typical value = 0,5.
trSecondsWashout time constant (<i>Tr</i>) (> 0). Typical value = 5.
twSecondsWater inertia time constant (<i>Tw</i>) (> 0). Typical value = 1.
velmFloatMaximum gate velocity (<i>Vlem</i>) (> 0). Typical value = 0,2.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None