GovSteamEU

Class Description

Simplified boiler and steam turbine with PID governor.

Attributes

NameTypeDescription
chcFloatControl valves rate closing limit (<i>Chc</i>). Unit = PU / s. Typical value = -3,3.
choFloatControl valves rate opening limit (<i>Cho</i>). Unit = PU / s. Typical value = 0,17.
cicPUIntercept valves rate closing limit (<i>Cic</i>). Typical value = -2,2.
cioPUIntercept valves rate opening limit (<i>Cio</i>). Typical value = 0,123.
db1PUDeadband of the frequency corrector (<i>db1</i>). Typical value = 0.
db2PUDeadband of the speed governor (<i>db2</i>). Typical value = 0,0004.
hhpmaxPUMaximum control valve position (<i>Hhpmax</i>). Typical value = 1.
kePUGain of the power controller (<i>Ke</i>). Typical value = 0,65.
kfcorPUGain of the frequency corrector (<i>Kfcor</i>). Typical value = 20.
khpPUFraction of total turbine output generated by HP part (<i>Khp</i>). Typical value = 0,277.
klpPUFraction of total turbine output generated by HP part (<i>Klp</i>). Typical value = 0,723.
komegacorPUGain of the speed governor (<i>Kwcor</i>). Typical value = 20.
mwbaseActivePowerBase for power values (<i>MWbase</i>) (> 0). Unit = MW.
pmaxPUMaximal active power of the turbine (<i>Pmax</i>). Typical value = 1.
prhmaxPUMaximum low pressure limit (<i>Prhmax</i>). Typical value = 1,4.
simxPUIntercept valves transfer limit (<i>Simx</i>). Typical value = 0,425.
tbSecondsBoiler time constant (<i>Tb</i>) (>= 0). Typical value = 100.
tdpSecondsDerivative time constant of the power controller (<i>Tdp</i>) (>= 0). Typical value = 0.
tenSecondsElectro hydraulic transducer (<i>Ten</i>) (>= 0). Typical value = 0,1.
tfSecondsFrequency transducer time constant (<i>Tf</i>) (>= 0). Typical value = 0.
tfpSecondsTime constant of the power controller (<i>Tfp</i>) (>= 0). Typical value = 0.
thpSecondsHigh pressure (HP) time constant of the turbine (<i>Thp</i>) (>= 0). Typical value = 0,31.
tipSecondsIntegral time constant of the power controller (<i>Tip</i>) (>= 0). Typical value = 2.
tlpSecondsLow pressure (LP) time constant of the turbine (<i>Tlp</i>) (>= 0). Typical value = 0,45.
tpSecondsPower transducer time constant (<i>Tp</i>) (>= 0). Typical value = 0,07.
trhSecondsReheater time constant of the turbine (<i>Trh</i>) (>= 0). Typical value = 8.
tvhpSecondsControl valves servo time constant (<i>Tvhp</i>) (>= 0). Typical value = 0,1.
tvipSecondsIntercept valves servo time constant (<i>Tvip</i>) (>= 0). Typical value = 0,15.
twSecondsSpeed transducer time constant (<i>Tw</i>) (>= 0). Typical value = 0,02.
wfmaxPUUpper limit for frequency correction (<i>Wfmax</i>) (> GovSteamEU.wfmin). Typical value = 0,05.
wfminPULower limit for frequency correction (<i>Wfmin</i>) (< GovSteamEU.wfmax). Typical value = -0,05.
wmax1PUEmergency speed control lower limit (<i>wmax1</i>). Typical value = 1,025.
wmax2PUEmergency speed control upper limit (<i>wmax2</i>). Typical value = 1,05.
wwmaxPUUpper limit for the speed governor (<i>Wwmax</i>) (> GovSteamEU.wwmin). Typical value = 0,1.
wwminPULower limit for the speed governor frequency correction (<i>Wwmin</i>) (< GovSteamEU.wwmax). Typical value = -1.