Class Description

General governor with frequency-dependent fuel flow limit. This model is a modification of the GovCT1<b> </b>model in order to represent the frequency-dependent fuel flow limit of a specific gas turbine manufacturer.

Attributes

NameTypeDescription
asetFloatAcceleration limiter setpoint (<i>Aset</i>). Unit = PU / s. Typical value = 10.
dbPUSpeed governor deadband in PU speed (<i>db</i>). In the majority of applications, it is recommended that this value be set to zero. Typical value = 0.
dmPUSpeed sensitivity coefficient (<i>Dm</i>). <i>Dm</i> can represent either the variation of the engine power with the shaft speed or the variation of maximum power capability with shaft speed. If it is positive it describes the falling slope of the engine speed verses power characteristic as speed increases. A slightly falling characteristic is typical for reciprocating engines and some aero-derivative turbines. If it is negative the engine power is assumed to be unaffected by the shaft speed, but the maximum permissible fuel flow is taken to fall with falling shaft speed. This is characteristic of single-shaft industrial turbines due to exhaust temperature limits. Typical value = 0.
flim1FrequencyFrequency threshold 1 (<i>Flim1</i>). Unit = Hz. Typical value = 59.
flim10FrequencyFrequency threshold 10 (<i>Flim10</i>). Unit = Hz. Typical value = 0.
flim2FrequencyFrequency threshold 2 (<i>Flim2</i>). Unit = Hz. Typical value = 0.
flim3FrequencyFrequency threshold 3 (<i>Flim3</i>). Unit = Hz. Typical value = 0.
flim4FrequencyFrequency threshold 4 (<i>Flim4</i>). Unit = Hz. Typical value = 0.
flim5FrequencyFrequency threshold 5 (<i>Flim5</i>). Unit = Hz. Typical value = 0.
flim6FrequencyFrequency threshold 6 (<i>Flim6</i>). Unit = Hz. Typical value = 0.
flim7FrequencyFrequency threshold 7 (<i>Flim7</i>). Unit = Hz. Typical value = 0.
flim8FrequencyFrequency threshold 8 (<i>Flim8</i>). Unit = Hz. Typical value = 0.
flim9FrequencyFrequency threshold 9 (<i>Flim9</i>). Unit = Hz. Typical value = 0.
kaPUAcceleration limiter gain (<i>Ka</i>). Typical value = 10.
kdgovPUGovernor derivative gain (<i>Kdgov</i>). Typical value = 0.
kigovPUGovernor integral gain (<i>Kigov</i>). Typical value = 0,45.
kiloadPULoad limiter integral gain for PI controller (<i>Kiload</i>). Typical value = 1.
kimwPUPower controller (reset) gain (<i>Kimw</i>). The default value of 0,01 corresponds to a reset time of 100 seconds. A value of 0,001 corresponds to a relatively slow-acting load controller. Typical value = 0.
kpgovPUGovernor proportional gain (<i>Kpgov</i>). Typical value = 4.
kploadPULoad limiter proportional gain for PI controller (<i>Kpload</i>). Typical value = 1.
kturbPUTurbine gain (<i>Kturb</i>). Typical value = 1,9168.
ldrefPULoad limiter reference value (<i>Ldref</i>). Typical value = 1.
maxerrPUMaximum value for speed error signal (<i>Maxerr</i>) (> GovCT2.minerr). Typical value = 1.
minerrPUMinimum value for speed error signal (<i>Minerr</i>) (< GovCT2.maxerr). Typical value = -1.
mwbaseActivePowerBase for power values (<i>MWbase</i>) (> 0). Unit = MW.
plim1PUPower limit 1 (<i>Plim1</i>). Typical value = 0,8325.
plim10PUPower limit 10 (<i>Plim10</i>). Typical value = 0.
plim2PUPower limit 2 (Plim2). Typical value = 0.
plim3PUPower limit 3 (<i>Plim3</i>). Typical value = 0.
plim4PUPower limit 4 (<i>Plim4</i>). Typical value = 0.
plim5PUPower limit 5 (<i>Plim5</i>). Typical value = 0.
plim6PUPower limit 6 (<i>Plim6</i>). Typical value = 0.
plim7PUPower limit 7 (<i>Plim7</i>). Typical value = 0.
plim8PUPower limit 8 (<i>Plim8</i>). Typical value = 0.
plim9PUPower Limit 9 (<i>Plim9</i>). Typical value = 0.
pratePURamp rate for frequency-dependent power limit (<i>Prate</i>). Typical value = 0,017.
rPUPermanent droop (<i>R</i>). Typical value = 0,05.
rcloseFloatMinimum valve closing rate (<i>Rclose</i>). Unit = PU / s. Typical value = -99.
rdownPUMaximum rate of load limit decrease (<i>Rdown</i>). Typical value = -99.
ropenFloatMaximum valve opening rate (<i>Ropen</i>). Unit = PU / s. Typical value = 99.
rselectDroopSignalFeedbackKindFeedback signal for droop (<i>Rselect</i>). Typical value = electricalPower.
rupPUMaximum rate of load limit increase (<i>Rup</i>). Typical value = 99.
taSecondsAcceleration limiter time constant (<i>Ta</i>) (>= 0). Typical value = 1.
tactSecondsActuator time constant (<i>Tact</i>) (>= 0). Typical value = 0,4.
tbSecondsTurbine lag time constant (<i>Tb</i>) (>= 0). Typical value = 0,1.
tcSecondsTurbine lead time constant (<i>Tc</i>) (>= 0). Typical value = 0.
tdgovSecondsGovernor derivative controller time constant (<i>Tdgov</i>) (>= 0). Typical value = 1.
tengSecondsTransport time delay for diesel engine used in representing diesel engines where there is a small but measurable transport delay between a change in fuel flow setting and the development of torque (<i>Teng</i>) (>= 0). <i>Teng</i> should be zero in all but special cases where this transport delay is of particular concern. Typical value = 0.
tfloadSecondsLoad limiter time constant (<i>Tfload</i>) (>= 0). Typical value = 3.
tpelecSecondsElectrical power transducer time constant (<i>Tpelec</i>) (>= 0). Typical value = 2,5.
tsaSecondsTemperature detection lead time constant (<i>Tsa</i>) (>= 0). Typical value = 0.
tsbSecondsTemperature detection lag time constant (<i>Tsb</i>) (>= 0). Typical value = 50.
vmaxPUMaximum valve position limit (<i>Vmax</i>) (> GovCT2.vmin). Typical value = 1.
vminPUMinimum valve position limit (<i>Vmin</i>) (< GovCT2.vmax). Typical value = 0,175.
wfnlPUNo load fuel flow (<i>Wfnl</i>). Typical value = 0,187.
wfspdBooleanSwitch for fuel source characteristic to recognize that fuel flow, for a given fuel valve stroke, can be proportional to engine speed (<i>Wfspd</i>).
true = fuel flow proportional to speed (for some gas turbines and diesel engines with positive displacement fuel injectors)
false = fuel control system keeps fuel flow independent of engine speed.
Typical value = false.