Skip to main content

GovGAST3

Class Description

Generic turbogas with acceleration and temperature controller.

Attributes

NameTypeDescription
bcaFloatAcceleration limit set-point (<i>Bca</i>). Unit = 1/s. Typical value = 0,01.
bpPUDroop (<i>bp</i>). Typical value = 0,05.
dtcTemperatureExhaust temperature variation due to fuel flow increasing from 0 to 1 PU (<i>deltaTc</i>). Typical value = 390.
kaPUMinimum fuel flow (<i>Ka</i>). Typical value = 0,23.
kacFloatFuel system feedback (<i>K</i><i><sub>AC</sub></i>). Typical value = 0.
kcaFloatAcceleration control integral gain (<i>Kca</i>). Unit = 1/s. Typical value = 100.
ksiFloatGain of radiation shield (<i>Ksi</i>). Typical value = 0,8.
kyFloatCoefficient of transfer function of fuel valve positioner (<i>Ky</i>). Typical value = 1.
mnefPUFuel flow maximum negative error value (<i>MNef</i>). Typical value = -0,05.
mxefPUFuel flow maximum positive error value (<i>MXef</i>). Typical value = 0,05.
rcmnPUMinimum fuel flow (<i>RCMN</i>). Typical value = -0,1.
rcmxPUMaximum fuel flow (<i>RCMX</i>). Typical value = 1.
tacSecondsFuel control time constant (<i>Tac</i>) (>= 0). Typical value = 0,1.
tcSecondsCompressor discharge volume time constant (<i>Tc</i>) (>= 0). Typical value = 0,2.
tdSecondsTemperature controller derivative gain (<i>Td</i>) (>= 0). Typical value = 3,3.
tfenTemperatureTurbine rated exhaust temperature correspondent to Pm=1 PU (<i>Tfen</i>). Typical value = 540.
tgSecondsTime constant of speed governor (<i>Tg</i>) (>= 0). Typical value = 0,05.
tsiSecondsTime constant of radiation shield (<i>Tsi</i>) (>= 0). Typical value = 15.
ttTemperatureTemperature controller integration rate (<i>Tt</i>). Typical value = 250.
ttcSecondsTime constant of thermocouple (<i>Ttc</i>) (>= 0). Typical value = 2,5.
tySecondsTime constant of fuel valve positioner (<i>Ty</i>) (>= 0). Typical value = 0,2.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None