Name | Type | Description |
---|---|---|
at | PU | Turbine gain (<i>At</i>). Typical value = 1,2. |
db1 | Frequency | Intentional dead-band width (<i>db1</i>). Unit = Hz. Typical value = 0. |
db2 | ActivePower | Unintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0. |
dturb | PU | Turbine damping factor (<i>Dturb</i>). Typical value = 0,2. |
eps | Frequency | Intentional db hysteresis (<i>eps</i>). Unit = Hz. Typical value = 0. |
gmax | PU | Maximum governor output (<i>Gmax</i>) (> GovHydroR.gmin). Typical value = 1,05. |
gmin | PU | Minimum governor output (<i>Gmin</i>) (< GovHydroR.gmax). Typical value = -0,05. |
gv1 | PU | Nonlinear gain point 1, PU gv (<i>Gv1</i>). Typical value = 0. |
gv2 | PU | Nonlinear gain point 2, PU gv (<i>Gv2</i>). Typical value = 0. |
gv3 | PU | Nonlinear gain point 3, PU gv (<i>Gv3</i>). Typical value = 0. |
gv4 | PU | Nonlinear gain point 4, PU gv (<i>Gv4</i>). Typical value = 0. |
gv5 | PU | Nonlinear gain point 5, PU gv (<i>Gv5</i>). Typical value = 0. |
gv6 | PU | Nonlinear gain point 6, PU gv (<i>Gv6</i>). Typical value = 0. |
h0 | PU | Turbine nominal head (<i>H0</i>). Typical value = 1. |
inputSignal | Boolean | Input signal switch (<i>Flag</i>). true = <i>Pe</i> input is used false = feedback is received from <i>CV</i>. <i>Flag</i> is normally dependent on <i>Tt</i>. If <i>Tt </i>is zero, <i>Flag</i> is set to false. If <i>Tt</i> is not zero, <i>Flag</i> is set to true. Typical value = true. |
kg | PU | Gate servo gain (<i>Kg</i>). Typical value = 2. |
ki | PU | Integral gain (<i>Ki</i>). Typical value = 0,5. |
mwbase | ActivePower | Base for power values (<i>MWbase</i>) (> 0). Unit = MW. |
pgv1 | PU | Nonlinear gain point 1, PU power (<i>Pgv1</i>). Typical value = 0. |
pgv2 | PU | Nonlinear gain point 2, PU power (<i>Pgv2</i>). Typical value = 0. |
pgv3 | PU | Nonlinear gain point 3, PU power (<i>Pgv3</i>). Typical value = 0. |
pgv4 | PU | Nonlinear gain point 4, PU power (<i>Pgv4</i>). Typical value = 0. |
pgv5 | PU | Nonlinear gain point 5, PU power (<i>Pgv5</i>). Typical value = 0. |
pgv6 | PU | Nonlinear gain point 6, PU power (<i>Pgv6</i>). Typical value = 0. |
pmax | PU | Maximum gate opening, PU of <i>MWbase</i> (<i>Pmax</i>) (> GovHydroR.pmin). Typical value = 1. |
pmin | PU | Minimum gate opening, PU of <i>MWbase</i> (<i>Pmin</i>) (< GovHydroR.pmax). Typical value = 0. |
qnl | PU | No-load turbine flow at nominal head (<i>Qnl</i>). Typical value = 0,08. |
r | PU | Steady-state droop (<i>R</i>). Typical value = 0,05. |
t1 | Seconds | Lead time constant 1 (<i>T1</i>) (>= 0). Typical value = 1,5. |
t2 | Seconds | Lag time constant 1 (<i>T2</i>) (>= 0). Typical value = 0,1. |
t3 | Seconds | Lead time constant 2 (<i>T3</i>) (>= 0). Typical value = 1,5. |
t4 | Seconds | Lag time constant 2 (<i>T4</i>) (>= 0). Typical value = 0,1. |
t5 | Seconds | Lead time constant 3 (<i>T5</i>) (>= 0). Typical value = 0. |
t6 | Seconds | Lag time constant 3 (<i>T6</i>) (>= 0). Typical value = 0,05. |
t7 | Seconds | Lead time constant 4 (<i>T7</i>) (>= 0). Typical value = 0. |
t8 | Seconds | Lag time constant 4 (<i>T8</i>) (>= 0). Typical value = 0,05. |
td | Seconds | Input filter time constant (<i>Td</i>) (>= 0). Typical value = 0,05. |
tp | Seconds | Gate servo time constant (<i>Tp</i>) (>= 0). Typical value = 0,05. |
tt | Seconds | Power feedback time constant (<i>Tt</i>) (>= 0). Typical value = 0. |
tw | Seconds | Water inertia time constant (<i>Tw</i>) (> 0). Typical value = 1. |
velcl | Float | Maximum gate closing velocity (<i>Velcl</i>). Unit = PU / s. Typical value = -0,2. |
velop | Float | Maximum gate opening velocity (<i>Velop</i>). Unit = PU / s. Typical value = 0,2. |