Class Description

Woodward<sup>TM</sup> PID hydro governor. [Footnote: Woodward PID hydro governors are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]

Attributes

NameTypeDescription
dPUTurbine damping factor (<i>D</i>). Unit = delta P / delta speed.
gatmaxPUGate opening limit maximum (<i>Gatmax</i>) (> GovHydroWPID.gatmin).
gatminPUGate opening limit minimum (<i>Gatmin</i>) (< GovHydroWPID.gatmax).
gv1PUGate position 1 (<i>Gv1</i>).
gv2PUGate position 2 (<i>Gv2</i>).
gv3PUGate position 3 (<i>Gv3</i>) (= 1,0).
kdPUDerivative gain (<i>Kd</i>). Typical value = 1,11.
kiPUReset gain (<i>Ki</i>). Typical value = 0,36.
kpPUProportional gain (<i>Kp</i>). Typical value = 0,1.
mwbaseActivePowerBase for power values (<i>MWbase</i>) (> 0). Unit = MW.
pgv1PUOutput at <i>Gv1</i> PU of <i>MWbase</i> (<i>Pgv1</i>).
pgv2PUOutput at <i>Gv2</i> PU of <i>MWbase</i> (<i>Pgv2</i>).
pgv3PUOutput at <i>Gv3</i> PU of <i>MWbase</i> (<i>Pgv3</i>).
pmaxPUMaximum power output (<i>Pmax</i>) (> GovHydroWPID.pmin).
pminPUMinimum power output (<i>Pmin</i>) (< GovHydroWPID.pmax).
regPUPermanent drop (<i>Reg</i>).
taSecondsController time constant (<i>Ta</i>) (>= 0). Typical value = 0.
tbSecondsGate servo time constant (<i>Tb</i>) (>= 0). Typical value = 0.
tregSecondsSpeed detector time constant (<i>Treg</i>) (>= 0).
twSecondsWater inertia time constant (<i>Tw</i>) (>= 0). Typical value = 0.
velmaxPUMaximum gate opening velocity (<i>Velmax</i>) (> GovHydroWPID.velmin). Unit = PU / s. Typical value = 0.
velminPUMaximum gate closing velocity (<i>Velmin</i>) (< GovHydroWPID.velmax). Unit = PU / s. Typical value = 0.

Relationships

Ancestors

Descendents

No descendent classes

Associations