GovSteamFV4
Class Description
Detailed electro-hydraulic governor for steam unit.
Attributes
Name | Type | Description |
---|---|---|
cpsmn | PU | Minimum value of pressure regulator output (<i>Cpsmn</i>). Typical value = -1. |
cpsmx | PU | Maximum value of pressure regulator output (<i>Cpsmx</i>). Typical value = 1. |
crmn | PU | Minimum value of regulator set-point (<i>Crmn</i>). Typical value = 0. |
crmx | PU | Maximum value of regulator set-point (<i>Crmx</i>). Typical value = 1,2. |
kdc | PU | Derivative gain of pressure regulator (<i>Kdc</i>). Typical value = 1. |
kf1 | PU | Frequency bias (reciprocal of droop) (<i>Kf1</i>). Typical value = 20. |
kf3 | PU | Frequency control (reciprocal of droop) (<i>Kf3</i>). Typical value = 20. |
khp | PU | Fraction of total turbine output generated by HP part (<i>Khp</i>). Typical value = 0,35. |
kic | PU | Integral gain of pressure regulator (<i>Kic</i>). Typical value = 0,0033. |
kip | PU | Integral gain of pressure feedback regulator (<i>Kip</i>). Typical value = 0,5. |
kit | PU | Integral gain of electro-hydraulic regulator (<i>Kit</i>). Typical value = 0,04. |
kmp1 | PU | First gain coefficient of intercept valves characteristic (<i>Kmp1</i>). Typical value = 0,5. |
kmp2 | PU | Second gain coefficient of intercept valves characteristic (<i>Kmp2</i>). Typical value = 3,5. |
kpc | PU | Proportional gain of pressure regulator (<i>Kpc</i>). Typical value = 0,5. |
kpp | PU | Proportional gain of pressure feedback regulator (<i>Kpp</i>). Typical value = 1. |
kpt | PU | Proportional gain of electro-hydraulic regulator (<i>Kpt</i>). Typical value = 0,3. |
krc | PU | Maximum variation of fuel flow (<i>Krc</i>). Typical value = 0,05. |
ksh | PU | Pressure loss due to flow friction in the boiler tubes (<i>Ksh</i>). Typical value = 0,08. |
lpi | PU | Maximum negative power error (<i>Lpi</i>). Typical value = -0,15. |
lps | PU | Maximum positive power error (<i>Lps</i>). Typical value = 0,03. |
mnef | PU | Lower limit for frequency correction (<i>MN</i><i><sub>EF</sub></i>). Typical value = -0,05. |
mxef | PU | Upper limit for frequency correction (<i>MX</i><i><sub>EF</sub></i>). Typical value = 0,05. |
pr1 | PU | First value of pressure set point static characteristic (<i>Pr1</i>). Typical value = 0,2. |
pr2 | PU | Second value of pressure set point static characteristic, corresponding to <i>Ps0</i> = 1,0 PU (<i>Pr2</i>). Typical value = 0,75. |
psmn | PU | Minimum value of pressure set point static characteristic (<i>Psmn</i>). Typical value = 1. |
rsmimn | PU | Minimum value of integral regulator (<i>Rsmimn</i>). Typical value = 0. |
rsmimx | PU | Maximum value of integral regulator (<i>Rsmimx</i>). Typical value = 1,1. |
rvgmn | PU | Minimum value of integral regulator (<i>Rvgmn</i>). Typical value = 0. |
rvgmx | PU | Maximum value of integral regulator (<i>Rvgmx</i>). Typical value = 1,2. |
srmn | PU | Minimum valve opening (<i>Srmn</i>). Typical value = 0. |
srmx | PU | Maximum valve opening (<i>Srmx</i>). Typical value = 1,1. |
srsmp | PU | Intercept valves characteristic discontinuity point (<i>Srsmp</i>). Typical value = 0,43. |
svmn | Float | Maximum regulator gate closing velocity (<i>Svmn</i>). Typical value = -0,0333. |
svmx | Float | Maximum regulator gate opening velocity (<i>Svmx</i>). Typical value = 0,0333. |
ta | Seconds | Control valves rate opening time (<i>Ta</i>) (>= 0). Typical value = 0,8. |
tam | Seconds | Intercept valves rate opening time (<i>Tam</i>) (>= 0). Typical value = 0,8. |
tc | Seconds | Control valves rate closing time (<i>Tc</i>) (>= 0). Typical value = 0,5. |
tcm | Seconds | Intercept valves rate closing time (<i>Tcm</i>) (>= 0). Typical value = 0,5. |
tdc | Seconds | Derivative time constant of pressure regulator (<i>Tdc</i>) (>= 0). Typical value = 90. |
tf1 | Seconds | Time constant of fuel regulation (<i>Tf1</i>) (>= 0). Typical value = 10. |
tf2 | Seconds | Time constant of steam chest (<i>Tf2</i>) (>= 0). Typical value = 10. |
thp | Seconds | High pressure (HP) time constant of the turbine (<i>Thp</i>) (>= 0). Typical value = 0,15. |
tmp | Seconds | Low pressure (LP) time constant of the turbine (<i>Tmp</i>) (>= 0). Typical value = 0,4. |
trh | Seconds | Reheater time constant of the turbine (<i>Trh</i>) (>= 0). Typical value = 10. |
tv | Seconds | Boiler time constant (<i>Tv</i>) (>= 0). Typical value = 60. |
ty | Seconds | Control valves servo time constant (<i>Ty</i>) (>= 0). Typical value = 0,1. |
y | PU | Coefficient of linearized equations of turbine (Stodola formulation) (<i>Y</i>). Typical value = 0,13. |
yhpmn | PU | Minimum control valve position (<i>Yhpmn</i>). Typical value = 0. |
yhpmx | PU | Maximum control valve position (<i>Yhpmx</i>). Typical value = 1,1. |
ympmn | PU | Minimum intercept valve position (<i>Ympmn</i>). Typical value = 0. |
ympmx | PU | Maximum intercept valve position (<i>Ympmx</i>). Typical value = 1,1. |
Relationships
Ancestors
Descendents
No descendent classes
Associations
None