Skip to main content

GovGAST1

Class Description

Modified single shaft gas turbine.

Attributes

NameTypeDescription
aFloatTurbine power time constant numerator scale factor (<i>a</i>). Typical value = 0,8.
bFloatTurbine power time constant denominator scale factor (<i>b</i>) (>0). Typical value = 1.
db1FrequencyIntentional dead-band width (<i>db1</i>). Unit = Hz. Typical value = 0.
db2ActivePowerUnintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0.
epsFrequencyIntentional db hysteresis (<i>eps</i>). Unit = Hz. Typical value = 0.
fidlePUFuel flow at zero power output (<i>Fidle</i>). Typical value = 0,18.
gv1PUNonlinear gain point 1, PU gv (<i>Gv1</i>). Typical value = 0.
gv2PUNonlinear gain point 2,PU gv (<i>Gv2</i>). Typical value = 0.
gv3PUNonlinear gain point 3, PU gv (<i>Gv3</i>). Typical value = 0.
gv4PUNonlinear gain point 4, PU gv (<i>Gv4</i>). Typical value = 0.
gv5PUNonlinear gain point 5, PU gv (<i>Gv5</i>). Typical value = 0.
gv6PUNonlinear gain point 6, PU gv (<i>Gv6</i>). Typical value = 0.
kaPUGovernor gain (<i>Ka</i>). Typical value = 0.
ktPUTemperature limiter gain (<i>Kt</i>). Typical value = 3.
lmaxPUAmbient temperature load limit (<i>Lmax</i>). <i>Lmax</i> is the turbine power output corresponding to the limiting exhaust gas temperature. Typical value = 1.
loadincPUValve position change allowed at fast rate (<i>Loadinc</i>). Typical value = 0,05.
ltrateFloatMaximum long term fuel valve opening rate (<i>Ltrate</i>). Typical value = 0,02.
mwbaseActivePowerBase for power values (<i>MWbase</i>) (> 0). Unit = MW.
pgv1PUNonlinear gain point 1, PU power (<i>Pgv1</i>). Typical value = 0.
pgv2PUNonlinear gain point 2, PU power (<i>Pgv2</i>). Typical value = 0.
pgv3PUNonlinear gain point 3, PU power (<i>Pgv3</i>). Typical value = 0.
pgv4PUNonlinear gain point 4, PU power (<i>Pgv4</i>). Typical value = 0.
pgv5PUNonlinear gain point 5, PU power (<i>Pgv5</i>). Typical value = 0.
pgv6PUNonlinear gain point 6, PU power (<i>Pgv6</i>). Typical value = 0.
rPUPermanent droop (<i>R</i>) (>0). Typical value = 0,04.
rmaxFloatMaximum fuel valve opening rate (<i>Rmax</i>). Unit = PU / s. Typical value = 1.
t1SecondsGovernor mechanism time constant (<i>T1</i>) (>= 0). <i>T1</i> represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical value = 0,5.
t2SecondsTurbine power time constant (<i>T2</i>) (>= 0). <i>T2</i> represents delay due to internal energy storage of the gas turbine engine. <i>T2</i> can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi-shaft engine, or with the compressibility of gas in the plenum of the free power turbine of an aero-derivative unit, for example. Typical value = 0,5.
t3SecondsTurbine exhaust temperature time constant (<i>T3</i>) (>= 0). <i>T3</i> represents delay in the exhaust temperature and load limiting system. Typical value = 3.
t4SecondsGovernor lead time constant (<i>T4</i>) (>= 0). Typical value = 0.
t5SecondsGovernor lag time constant (<i>T5</i>) (>= 0). If = 0, entire gain and lead-lag block is bypassed. Typical value = 0.
tltrSecondsValve position averaging time constant (<i>Tltr</i>) (>= 0). Typical value = 10.
vmaxPUMaximum turbine power, PU of MWbase (<i>Vmax</i>) (> GovGAST1.vmin). Typical value = 1.
vminPUMinimum turbine power, PU of MWbase (<i>Vmin</i>) (< GovGAST1.vmax). Typical value = 0.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None