Skip to main content

GovHydro2

Class Description

IEEE hydro turbine governor with straightforward penstock configuration and hydraulic-dashpot governor.

Attributes

NameTypeDescription
aturbPUTurbine numerator multiplier (<i>Aturb</i>). Typical value = -1.
bturbPUTurbine denominator multiplier (<i>Bturb</i>) (> 0). Typical value = 0,5.
db1FrequencyIntentional deadband width (<i>db1</i>). Unit = Hz. Typical value = 0.
db2ActivePowerUnintentional deadband (<i>db2</i>). Unit = MW. Typical value = 0.
epsFrequencyIntentional db hysteresis (<i>eps</i>). Unit = Hz. Typical value = 0.
gv1PUNonlinear gain point 1, PU gv (<i>Gv1</i>). Typical value = 0.
gv2PUNonlinear gain point 2, PU gv (<i>Gv2</i>). Typical value = 0.
gv3PUNonlinear gain point 3, PU gv (<i>Gv3</i>). Typical value = 0.
gv4PUNonlinear gain point 4, PU gv (<i>Gv4</i>). Typical value = 0.
gv5PUNonlinear gain point 5, PU gv (<i>Gv5</i>). Typical value = 0.
gv6PUNonlinear gain point 6, PU gv (<i>Gv6</i>). Typical value = 0.
kturbPUTurbine gain (<i>Kturb</i>). Typical value = 1.
mwbaseActivePowerBase for power values (<i>MWbase</i>) (> 0). Unit = MW.
pgv1PUNonlinear gain point 1, PU power (<i>Pgv1</i>). Typical value = 0.
pgv2PUNonlinear gain point 2, PU power (<i>Pgv2</i>). Typical value = 0.
pgv3PUNonlinear gain point 3, PU power (<i>Pgv3</i>). Typical value = 0.
pgv4PUNonlinear gain point 4, PU power (P<i>gv4</i>). Typical value = 0.
pgv5PUNonlinear gain point 5, PU power (<i>Pgv5</i>). Typical value = 0.
pgv6PUNonlinear gain point 6, PU power (<i>Pgv6</i>). Typical value = 0.
pmaxPUMaximum gate opening (<i>Pmax</i>) (> GovHydro2.pmin). Typical value = 1.
pminPUMinimum gate opening (<i>Pmin</i>) (< GovHydro2.pmax). Typical value = 0.
rpermPUPermanent droop (<i>Rperm</i>). Typical value = 0,05.
rtempPUTemporary droop (<i>Rtemp</i>). Typical value = 0,5.
tgSecondsGate servo time constant (<i>Tg</i>) (> 0). Typical value = 0,5.
tpSecondsPilot servo valve time constant (<i>Tp</i>) (>= 0). Typical value = 0,03.
trSecondsDashpot time constant (<i>Tr</i>) (>= 0). Typical value = 12.
twSecondsWater inertia time constant (<i>Tw</i>) (>= 0). Typical value = 2.
ucFloatMaximum gate closing velocity (<i>Uc</i>) (< 0). Unit = PU / s. Typical value = -0,1.
uoFloatMaximum gate opening velocity (<i>Uo</i>). Unit = PU / s. Typical value = 0,1.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None