TurbLCFB1

Class Description

Turbine load controller model developed by WECC. This model represents a supervisory turbine load controller that acts to maintain turbine power at a set value by continuous adjustment of the turbine governor speed-load reference. This model is intended to represent slow reset 'outer loop' controllers managing the action of the turbine governor.

Attributes

NameTypeDescription
dbPUController deadband (<i>db</i>). Typical value = 0.
emaxPUMaximum control error (<i>Emax</i>) (see parameter detail 4). Typical value = 0,02.
fbPUFrequency bias gain (<i>Fb</i>). Typical value = 0.
fbfBooleanFrequency bias flag (<i>Fbf</i>).
true = enable frequency bias
false = disable frequency bias.
Typical value = false.
irmaxPUMaximum turbine speed/load reference bias (<i>Irmax</i>) (see parameter detail 3). Typical value = 0.
kiPUIntegral gain (<i>Ki</i>). Typical value = 0.
kpPUProportional gain (<i>Kp</i>). Typical value = 0.
mwbaseActivePowerBase for power values (<i>MWbase</i>) (> 0). Unit = MW.
pbfBooleanPower controller flag (<i>Pbf</i>).
true = enable load controller
false = disable load controller.
Typical value = false.
pmwsetActivePowerPower controller setpoint (<i>Pmwset</i>) (see parameter detail 1). Unit = MW. Typical value = 0.
speedReferenceGovernorBooleanType of turbine governor reference (<i>Type</i>).
true = speed reference governor
false = load reference governor.
Typical value = true.
tpelecSecondsPower transducer time constant (<i>Tpelec</i>) (>= 0). Typical value = 0.