TurbLCFB1
Class Description
Turbine load controller model developed by WECC. This model represents a supervisory turbine load controller that acts to maintain turbine power at a set value by continuous adjustment of the turbine governor speed-load reference. This model is intended to represent slow reset 'outer loop' controllers managing the action of the turbine governor.
Attributes
Name | Type | Description |
---|---|---|
db | PU | Controller deadband (<i>db</i>). Typical value = 0. |
emax | PU | Maximum control error (<i>Emax</i>) (see parameter detail 4). Typical value = 0,02. |
fb | PU | Frequency bias gain (<i>Fb</i>). Typical value = 0. |
fbf | Boolean | Frequency bias flag (<i>Fbf</i>). true = enable frequency bias false = disable frequency bias. Typical value = false. |
irmax | PU | Maximum turbine speed/load reference bias (<i>Irmax</i>) (see parameter detail 3). Typical value = 0. |
ki | PU | Integral gain (<i>Ki</i>). Typical value = 0. |
kp | PU | Proportional gain (<i>Kp</i>). Typical value = 0. |
mwbase | ActivePower | Base for power values (<i>MWbase</i>) (> 0). Unit = MW. |
pbf | Boolean | Power controller flag (<i>Pbf</i>). true = enable load controller false = disable load controller. Typical value = false. |
pmwset | ActivePower | Power controller setpoint (<i>Pmwset</i>) (see parameter detail 1). Unit = MW. Typical value = 0. |
speedReferenceGovernor | Boolean | Type of turbine governor reference (<i>Type</i>). true = speed reference governor false = load reference governor. Typical value = true. |
tpelec | Seconds | Power transducer time constant (<i>Tpelec</i>) (>= 0). Typical value = 0. |
Relationships
Ancestors
Descendents
No descendent classes
Associations
None