GovHydroDD

Class Description

Double derivative hydro governor and turbine.

Attributes

NameTypeDescription
aturbPUTurbine numerator multiplier (<i>Aturb</i>) (see parameter detail 3). Typical value = -1.
bturbPUTurbine denominator multiplier (<i>Bturb</i>) (see parameter detail 3). Typical value = 0,5.
db1FrequencyIntentional dead-band width (<i>db1</i>). Unit = Hz. Typical value = 0.
db2ActivePowerUnintentional dead-band (<i>db2</i>). Unit = MW. Typical value = 0.
epsFrequencyIntentional db hysteresis (<i>eps</i>). Unit = Hz. Typical value = 0.
gmaxPUMaximum gate opening (<i>Gmax</i>) (> GovHydroDD.gmin). Typical value = 0.
gminPUMinimum gate opening (<i>Gmin</i>) (< GovHydroDD.gmax). Typical value = 0.
gv1PUNonlinear gain point 1, PU gv (<i>Gv1</i>). Typical value = 0.
gv2PUNonlinear gain point 2, PU gv (<i>Gv2</i>). Typical value = 0.
gv3PUNonlinear gain point 3, PU gv (<i>Gv3</i>). Typical value = 0.
gv4PUNonlinear gain point 4, PU gv (<i>Gv4</i>). Typical value = 0.
gv5PUNonlinear gain point 5, PU gv (<i>Gv5</i>). Typical value = 0.
gv6PUNonlinear gain point 6, PU gv (<i>Gv6</i>). Typical value = 0.
inputSignalBooleanInput signal switch (<i>Flag</i>).
true = <i>Pe</i> input is used
false = feedback is received from <i>CV</i>.
<i>Flag</i> is normally dependent on <i>Tt</i>. If <i>Tt</i> is zero, <i>Flag</i> is set to false. If <i>Tt</i> is not zero, <i>Flag</i> is set to true.
Typical value = true.
k1PUSingle derivative gain (<i>K1</i>). Typical value = 3,6.
k2PUDouble derivative gain (<i>K2</i>). Typical value = 0,2.
kgPUGate servo gain (<i>Kg</i>). Typical value = 3.
kiPUIntegral gain (<i>Ki</i>). Typical value = 1.
mwbaseActivePowerBase for power values (<i>MWbase</i>) (>0). Unit = MW.
pgv1PUNonlinear gain point 1, PU power (<i>Pgv1</i>). Typical value = 0.
pgv2PUNonlinear gain point 2, PU power (<i>Pgv2</i>). Typical value = 0.
pgv3PUNonlinear gain point 3, PU power (<i>Pgv3</i>). Typical value = 0.
pgv4PUNonlinear gain point 4, PU power (<i>Pgv4</i>). Typical value = 0.
pgv5PUNonlinear gain point 5, PU power (<i>Pgv5</i>). Typical value = 0.
pgv6PUNonlinear gain point 6, PU power (<i>Pgv6</i>). Typical value = 0.
pmaxPUMaximum gate opening, PU of <i>MWbase</i> (<i>Pmax</i>) (> GovHydroDD.pmin). Typical value = 1.
pminPUMinimum gate opening, PU of <i>MWbase</i> (<i>Pmin</i>) (> GovHydroDD.pmax). Typical value = 0.
rPUSteady state droop (<i>R</i>). Typical value = 0,05.
tdSecondsInput filter time constant (<i>Td</i>) (>= 0). If = 0, block is bypassed. Typical value = 0.
tfSecondsWashout time constant (<i>Tf</i>) (>= 0). Typical value = 0,1.
tpSecondsGate servo time constant (<i>Tp</i>) (>= 0). If = 0, block is bypassed. Typical value = 0,35.
ttSecondsPower feedback time constant (<i>Tt</i>) (>= 0). If = 0, block is bypassed. Typical value = 0,02.
tturbSecondsTurbine time constant (<i>Tturb</i>) (>= 0). See parameter detail 3. Typical value = 0,8.
velclFloatMaximum gate closing velocity (<i>Velcl</i>). Unit = PU / s. Typical value = -0,14.
velopFloatMaximum gate opening velocity (<i>Velop</i>). Unit = PU / s. Typical value = 0,09.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None