Skip to main content

ExcHU

Class Description

Hungarian excitation system, with built-in voltage transducer.

Attributes

NameTypeDescription
aePUMajor loop PI tag gain factor (<i>Ae</i>). Typical value = 3.
aiPUMinor loop PI tag gain factor (<i>Ai</i>). Typical value = 22.
atrPUAVR constant (<i>Atr</i>). Typical value = 2,19.
emaxPUField voltage control signal upper limit on AVR base (<i>Emax</i>) (> ExcHU.emin). Typical value = 0,996.
eminPUField voltage control signal lower limit on AVR base (<i>Emin</i>) (< ExcHU.emax). Typical value = -0,866.
imaxPUMajor loop PI tag output signal upper limit (<i>Imax</i>) (> ExcHU.imin). Typical value = 2,19.
iminPUMajor loop PI tag output signal lower limit (<i>Imin</i>) (< ExcHU.imax). Typical value = 0,1.
keFloatVoltage base conversion constant (<i>Ke</i>). Typical value = 4,666.
kiFloatCurrent base conversion constant (<i>Ki</i>). Typical value = 0,21428.
teSecondsMajor loop PI tag integration time constant (<i>Te</i>) (>= 0). Typical value = 0,154.
tiSecondsMinor loop PI control tag integration time constant (<i>Ti</i>) (>= 0). Typical value = 0,01333.
trSecondsFilter time constant (<i>Tr</i>) (>= 0). If a voltage compensator is used in conjunction with this excitation system model, <i>Tr </i>should be set to 0. Typical value = 0,01.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None