Skip to main content

ExcAC6A

Class Description

Modified IEEE AC6A alternator-supplied rectifier excitation system with speed input.

Attributes

NameTypeDescription
kaPUVoltage regulator gain (<i>Ka</i>) (> 0). Typical value = 536.
kcPURectifier loading factor proportional to commutating reactance (<i>Kc</i>) (>= 0). Typical value = 0,173.
kdPUDemagnetizing factor, a function of exciter alternator reactances (<i>Kd</i>) (>= 0). Typical value = 1,91.
kePUExciter constant related to self-excited field (<i>Ke</i>). Typical value = 1,6.
khPUExciter field current limiter gain (<i>Kh</i>) (>= 0). Typical value = 92.
ksPUCoefficient to allow different usage of the model-speed coefficient (<i>Ks</i>). Typical value = 0.
seve1FloatExciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>1</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>1</sub></i><i>]</i>) (>= 0). Typical value = 0,214.
seve2FloatExciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>2</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>2</sub></i><i>]</i>) (>= 0). Typical value = 0,044.
taSecondsVoltage regulator time constant (<i>Ta</i>) (>= 0). Typical value = 0,086.
tbSecondsVoltage regulator time constant (<i>Tb</i>) (>= 0). Typical value = 9.
tcSecondsVoltage regulator time constant (<i>Tc</i>) (>= 0). Typical value = 3.
teSecondsExciter time constant, integration rate associated with exciter control (<i>Te</i>) (> 0). Typical value = 1.
thSecondsExciter field current limiter time constant (<i>Th</i>) (> 0). Typical value = 0,08.
tjSecondsExciter field current limiter time constant (<i>Tj</i>) (>= 0). Typical value = 0,02.
tkSecondsVoltage regulator time constant (<i>Tk</i>) (>= 0). Typical value = 0,18.
vamaxPUMaximum voltage regulator output (<i>Vamax</i>) (> 0). Typical value = 75.
vaminPUMinimum voltage regulator output (<i>Vamin</i>) (< 0). Typical value = -75.
ve1PUExciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>1</sub></i>) (> 0). Typical value = 7,4.
ve2PUExciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>2</sub></i>) (> 0). Typical value = 5,55.
vfelimPUExciter field current limit reference (<i>Vfelim</i>) (> 0). Typical value = 19.
vhmaxPUMaximum field current limiter signal reference (<i>Vhmax</i>) (> 0). Typical value = 75.
vrmaxPUMaximum voltage regulator output (<i>Vrmax</i>) (> 0). Typical value = 44.
vrminPUMinimum voltage regulator output (<i>Vrmin</i>) (< 0). Typical value = -36.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None