Skip to main content

ExcIEEEAC1A

Class Description

IEEE 421.5-2005 type AC1A model. The model represents the field-controlled alternator-rectifier excitation systems designated type AC1A. These excitation systems consist of an alternator main exciter with non-controlled rectifiers. Reference: IEEE 421.5-2005, 6.1.

Attributes

NameTypeDescription
kaPUVoltage regulator gain (<i>K</i><i><sub>A</sub></i>) (> 0). Typical value = 400.
kcPURectifier loading factor proportional to commutating reactance (<i>K</i><i><sub>C</sub></i>) (>= 0). Typical value = 0,2.
kdPUDemagnetizing factor, a function of exciter alternator reactances (<i>K</i><i><sub>D</sub></i>) (>= 0). Typical value = 0,38.
kePUExciter constant related to self-excited field (<i>K</i><i><sub>E</sub></i>). Typical value = 1.
kfPUExcitation control system stabilizer gains (<i>K</i><i><sub>F</sub></i>) (>= 0). Typical value = 0,03.
seve1FloatExciter saturation function value at the corresponding exciter voltage, <i>V</i><i><sub>E1</sub></i>, back of commutating reactance (<i>S</i><i><sub>E</sub></i><i>[V</i><i><sub>E1</sub></i><i>]</i>) (>= 0). Typical value = 0,1.
seve2FloatExciter saturation function value at the corresponding exciter voltage, <i>V</i><i><sub>E2</sub></i>, back of commutating reactance (<i>S</i><i><sub>E</sub></i><i>[V</i><i><sub>E2</sub></i><i>]</i>) (>= 0). Typical value = 0,03.
taSecondsVoltage regulator time constant (<i>T</i><i><sub>A</sub></i>) (> 0). Typical value = 0,02.
tbSecondsVoltage regulator time constant (<i>T</i><i><sub>B</sub></i>) (>= 0). Typical value = 0.
tcSecondsVoltage regulator time constant (<i>T</i><i><sub>C</sub></i>) (>= 0). Typical value = 0.
teSecondsExciter time constant, integration rate associated with exciter control (<i>T</i><i><sub>E</sub></i>) (> 0). Typical value = 0,8.
tfSecondsExcitation control system stabilizer time constant (<i>T</i><i><sub>F</sub></i>) (> 0). Typical value = 1.
vamaxPUMaximum voltage regulator output (<i>V</i><i><sub>AMAX</sub></i>) (> 0). Typical value = 14,5.
vaminPUMinimum voltage regulator output (<i>V</i><i><sub>AMIN</sub></i>) (< 0). Typical value = -14,5.
ve1PUExciter alternator output voltages back of commutating reactance at which saturation is defined (<i>V</i><i><sub>E1</sub></i>) (> 0). Typical value = 4,18.
ve2PUExciter alternator output voltages back of commutating reactance at which saturation is defined (<i>V</i><i><sub>E2</sub></i>) (> 0). Typical value = 3,14.
vrmaxPUMaximum voltage regulator outputs (<i>V</i><i><sub>RMAX</sub></i>) (> 0). Typical value = 6,03.
vrminPUMinimum voltage regulator outputs (<i>V</i><i><sub>RMIN</sub></i>) (< 0). Typical value = -5,43.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None