ExcIEEEDC3A

Class Description

IEEE 421.5-2005 type DC3A model. This model represents older systems, in particular those DC commutator exciters with non-continuously acting regulators that were commonly used before the development of the continuously acting varieties. These systems respond at basically two different rates, depending upon the magnitude of voltage error. For small errors, adjustment is made periodically with a signal to a motor-operated rheostat. Larger errors cause resistors to be quickly shorted or inserted and a strong forcing signal applied to the exciter. Continuous motion of the motor-operated rheostat occurs for these larger error signals, even though it is bypassed by contactor action. Reference: IEEE 421.5-2005, 5.3.

Attributes

NameTypeDescription
efd1PUExciter voltage at which exciter saturation is defined (<i>E</i><i><sub>FD1</sub></i>) (> 0). Typical value = 3,375.
efd2PUExciter voltage at which exciter saturation is defined (<i>E</i><i><sub>FD2</sub></i>) (> 0). Typical value = 3,15.
exclimBoolean(<i>exclim</i>). IEEE standard is ambiguous about lower limit on exciter output.
true = a lower limit of zero is applied to integrator output
false = a lower limit of zero is not applied to integrator output.
Typical value = true.
kePUExciter constant related to self-excited field (<i>K</i><i><sub>E</sub></i>). Typical value = 0,05.
kvPUFast raise/lower contact setting (<i>K</i><i><sub>V</sub></i>) (> 0). Typical value = 0,05.
seefd1FloatExciter saturation function value at the corresponding exciter voltage, <i>E</i><i><sub>FD1</sub></i> (<i>S</i><i><sub>E</sub></i><i>[E</i><i><sub>FD1</sub></i><i>]</i>) (>= 0). Typical value = 0,267.
seefd2FloatExciter saturation function value at the corresponding exciter voltage, <i>E</i><i><sub>FD2</sub></i> (<i>S</i><i><sub>E</sub></i><i>[E</i><i><sub>FD2</sub></i><i>]</i>) (>= 0). Typical value = 0,068.
teSecondsExciter time constant, integration rate associated with exciter control (<i>T</i><i><sub>E</sub></i>) (> 0). Typical value = 0,5.
trhSecondsRheostat travel time (<i>T</i><i><sub>RH</sub></i>) (> 0). Typical value = 20.
vrmaxPUMaximum voltage regulator output (<i>V</i><i><sub>RMAX</sub></i>) (> 0). Typical value = 1.
vrminPUMinimum voltage regulator output (<i>V</i><i><sub>RMIN</sub></i>) (<= 0). Typical value = 0.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None