Skip to main content

ExcSK

Class Description

Slovakian excitation system. UEL and secondary voltage control are included in this model. When this model is used, there cannot be a separate underexcitation limiter or VAr controller model.

Attributes

NameTypeDescription
efdmaxPUField voltage clipping upper level limit (<i>Efdmax</i>) (> ExcSK.efdmin).
efdminPUField voltage clipping lower level limit (<i>Efdmin</i>) (< ExcSK.efdmax).
emaxPUMaximum field voltage output (<i>Emax</i>) (> ExcSK.emin). Typical value = 20.
eminPUMinimum field voltage output (<i>Emin</i>) (< ExcSK.emax). Typical value = -20.
kPUGain (<i>K</i>). Typical value = 1.
k1PUParameter of underexcitation limit (<i>K1</i>). Typical value = 0,1364.
k2PUParameter of underexcitation limit (<i>K2</i>). Typical value = -0,3861.
kcPUPI controller gain (<i>Kc</i>). Typical value = 70.
kcePURectifier regulation factor (<i>Kce</i>). Typical value = 0.
kdPUExciter internal reactance (<i>Kd</i>). Typical value = 0.
kgobPUP controller gain (<i>Kgob</i>). Typical value = 10.
kpPUPI controller gain (<i>Kp</i>). Typical value = 1.
kqiPUPI controller gain of integral component (<i>Kqi</i>). Typical value = 0.
kqobPURate of rise of the reactive power (<i>Kqob</i>).
kqpPUPI controller gain (<i>Kqp</i>). Typical value = 0.
nqPUDeadband of reactive power (<i>nq</i>). Determines the range of sensitivity. Typical value = 0,001.
qconoffBooleanSecondary voltage control state (<i>Qc_on_off</i>).
true = secondary voltage control is on
false = secondary voltage control is off.
Typical value = false.
qzPUDesired value (setpoint) of reactive power, manual setting (<i>Qz</i>).
remoteBooleanSelector to apply automatic calculation in secondary controller model (<i>remote</i>).
true = automatic calculation is activated
false = manual set is active; the use of desired value of reactive power (<i>Qz</i>) is required.
Typical value = true.
sbaseApparentPowerApparent power of the unit (<i>Sbase</i>) (> 0). Unit = MVA. Typical value = 259.
tcSecondsPI controller phase lead time constant (<i>Tc</i>) (>= 0). Typical value = 8.
teSecondsTime constant of gain block (<i>Te</i>) (>= 0). Typical value = 0,1.
tiSecondsPI controller phase lead time constant (<i>Ti</i>) (>= 0). Typical value = 2.
tpSecondsTime constant (<i>Tp</i>) (>= 0). Typical value = 0,1.
trSecondsVoltage transducer time constant (<i>Tr</i>) (>= 0). Typical value = 0,01.
uimaxPUMaximum error (<i>UImax</i>) (> ExcSK.uimin). Typical value = 10.
uiminPUMinimum error (<i>UImin</i>) (< ExcSK.uimax). Typical value = -10.
urmaxPUMaximum controller output (<i>URmax</i>) (> ExcSK.urmin). Typical value = 10.
urminPUMinimum controller output (<i>URmin</i>) (< ExcSK.urmax). Typical value = -10.
vtmaxPUMaximum terminal voltage input (<i>Vtmax</i>) (> ExcSK.vtmin). Determines the range of voltage deadband. Typical value = 1,05.
vtminPUMinimum terminal voltage input (<i>Vtmin</i>) (< ExcSK.vtmax). Determines the range of voltage deadband. Typical value = 0,95.
ypPUMaximum output (<i>Yp</i>). Typical value = 1.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None