ExcANS
Class Description
Italian excitation system. It represents static field voltage or excitation current feedback excitation system.
Attributes
Name | Type | Description |
---|---|---|
blint | Integer | Governor control flag (<i>BLINT</i>). 0 = lead-lag regulator 1 = proportional integral regulator. Typical value = 0. |
ifmn | PU | Minimum exciter current (<i>I</i><i><sub>FMN</sub></i>). Typical value = -5,2. |
ifmx | PU | Maximum exciter current (<i>I</i><i><sub>FMX</sub></i>). Typical value = 6,5. |
k2 | Float | Exciter gain (<i>K</i><i><sub>2</sub></i>). Typical value = 20. |
k3 | Float | AVR gain (<i>K</i><i><sub>3</sub></i>). Typical value = 1000. |
kce | Float | Ceiling factor (<i>K</i><i><sub>CE</sub></i>). Typical value = 1. |
krvecc | Integer | Feedback enabling (<i>K</i><i><sub>RVECC</sub></i>). 0 = open loop control 1 = closed loop control. Typical value = 1. |
kvfif | Integer | Rate feedback signal flag (<i>K</i><i><sub>VFIF</sub></i>). 0 = output voltage of the exciter 1 = exciter field current. Typical value = 0. |
t1 | Seconds | Time constant (<i>T</i><i><sub>1</sub></i>) (>= 0). Typical value = 20. |
t2 | Seconds | Time constant (<i>T</i><i><sub>2</sub></i>) (>= 0). Typical value = 0,05. |
t3 | Seconds | Time constant (<i>T</i><i><sub>3</sub></i>) (>= 0). Typical value = 1,6. |
tb | Seconds | Exciter time constant (<i>T</i><i><sub>B</sub></i>) (>= 0). Typical value = 0,04. |
vrmn | PU | Minimum AVR output (<i>V</i><i><sub>RMN</sub></i>). Typical value = -5,2. |
vrmx | PU | Maximum AVR output (<i>V</i><i><sub>RMX</sub></i>). Typical value = 6,5. |
Relationships
Ancestors
Descendents
No descendent classes
Associations
None