Skip to main content

ExcDC3A1

Class Description

Modified old IEEE type 3 excitation system.

Attributes

NameTypeDescription
exclimBoolean(<i>exclim</i>).
true = lower limit of zero is applied to integrator output
false = lower limit of zero not applied to integrator output.
Typical value = true.
kaPUVoltage regulator gain (<i>Ka</i>) (> 0). Typical value = 300.
kePUExciter constant related to self-excited field (<i>Ke</i>). Typical value = 1.
kfPUExcitation control system stabilizer gain (<i>Kf</i>) (>= 0). Typical value = 0,1.
kiPUPotential circuit gain coefficient (<i>Ki</i>) (>= 0). Typical value = 4,83.
kpPUPotential circuit gain coefficient (<i>Kp</i>) (>= 0). Typical value = 4,37.
taSecondsVoltage regulator time constant (<i>Ta</i>) (> 0). Typical value = 0,01.
teSecondsExciter time constant, integration rate associated with exciter control (<i>Te</i>) (> 0). Typical value = 1,83.
tfSecondsExcitation control system stabilizer time constant (<i>Tf</i>) (>= 0). Typical value = 0,675.
vb1maxPUAvailable exciter voltage limiter (<i>Vb1max</i>) (> 0). Typical value = 11,63.
vblimBooleanVb limiter indicator.
true = exciter <i>Vbmax</i> limiter is active
false = <i>Vb1max</i> is active.
Typical value = true.
vbmaxPUAvailable exciter voltage limiter (<i>Vbmax</i>) (> 0). Typical value = 11,63.
vrmaxPUMaximum voltage regulator output (<i>Vrmax</i>) (> ExcDC3A1.vrmin). Typical value = 5.
vrminPUMinimum voltage regulator output (<i>Vrmin</i>) (< 0 and < ExcDC3A1.vrmax). Typical value = 0.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None