Skip to main content

ExcIEEEAC6A

Class Description

IEEE 421.5-2005 type AC6A model. The model represents field-controlled alternator-rectifier excitation systems with system-supplied electronic voltage regulators. The maximum output of the regulator, <i>V</i><i><sub>R</sub></i>, is a function of terminal voltage, <i>V</i><i><sub>T</sub></i>. The field current limiter included in the original model AC6A remains in the 2005 update. Reference: IEEE 421.5-2005, 6.6.

Attributes

NameTypeDescription
kaPUVoltage regulator gain (<i>K</i><i><sub>A</sub></i>) (> 0). Typical value = 536.
kcPURectifier loading factor proportional to commutating reactance (<i>K</i><i><sub>C</sub></i>) (>= 0). Typical value = 0,173.
kdPUDemagnetizing factor, a function of exciter alternator reactances (<i>K</i><i><sub>D</sub></i>) (>= 0). Typical value = 1,91.
kePUExciter constant related to self-excited field (<i>K</i><i><sub>E</sub></i>). Typical value = 1,6.
khPUExciter field current limiter gain (<i>K</i><i><sub>H</sub></i>) (>= 0). Typical value = 92.
seve1FloatExciter saturation function value at the corresponding exciter voltage, <i>V</i><i><sub>E1</sub></i>, back of commutating reactance (<i>S</i><i><sub>E</sub></i><i>[V</i><i><sub>E1</sub></i><i>])</i> (>= 0). Typical value = 0,214.
seve2FloatExciter saturation function value at the corresponding exciter voltage, <i>V</i><i><sub>E2</sub></i>, back of commutating reactance (<i>S</i><i><sub>E</sub></i><i>[V</i><i><sub>E2</sub></i><i>]</i>) (>= 0). Typical value = 0,044.
taSecondsVoltage regulator time constant (<i>T</i><i><sub>A</sub></i>) (>= 0). Typical value = 0,086.
tbSecondsVoltage regulator time constant (<i>T</i><i><sub>B</sub></i>) (>= 0). Typical value = 9.
tcSecondsVoltage regulator time constant (<i>T</i><i><sub>C</sub></i>) (>= 0). Typical value = 3.
teSecondsExciter time constant, integration rate associated with exciter control (<i>T</i><i><sub>E</sub></i>) (> 0). Typical value = 1.
thSecondsExciter field current limiter time constant (<i>T</i><i><sub>H</sub></i>) (> 0). Typical value = 0,08.
tjSecondsExciter field current limiter time constant (<i>T</i><i><sub>J</sub></i>) (>= 0). Typical value = 0,02.
tkSecondsVoltage regulator time constant (<i>T</i><i><sub>K</sub></i>) (>= 0). Typical value = 0,18.
vamaxPUMaximum voltage regulator output (<i>V</i><i><sub>AMAX</sub></i>) (> 0). Typical value = 75.
vaminPUMinimum voltage regulator output (V<sub>AMIN</sub>) (< 0). Typical value = -75.
ve1PUExciter alternator output voltages back of commutating reactance at which saturation is defined (<i>V</i><i><sub>E1</sub></i>) (> 0). Typical value = 7,4.
ve2PUExciter alternator output voltages back of commutating reactance at which saturation is defined (<i>V</i><i><sub>E2</sub></i>) (> 0). Typical value = 5,55.
vfelimPUExciter field current limit reference (<i>V</i><i><sub>FELIM</sub></i>) (> 0). Typical value = 19.
vhmaxPUMaximum field current limiter signal reference (<i>V</i><i><sub>HMAX</sub></i>) (> 0). Typical value = 75.
vrmaxPUMaximum voltage regulator output (<i>V</i><i><sub>RMAX</sub></i>) (> 0). Typical value = 44.
vrminPUMinimum voltage regulator output (<i>V</i><i><sub>RMIN</sub></i>) (< 0). Typical value = -36.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None