Skip to main content

ExcAC8B

Class Description

Modified IEEE AC8B alternator-supplied rectifier excitation system with speed input and input limiter.

Attributes

NameTypeDescription
inlimBooleanInput limiter indicator.
true = input limiter <i>Vimax</i> and <i>Vimin</i> is considered
false = input limiter <i>Vimax </i>and <i>Vimin</i> is not considered.
Typical value = true.
kaPUVoltage regulator gain (<i>Ka</i>) (> 0). Typical value = 1.
kcPURectifier loading factor proportional to commutating reactance (<i>Kc</i>) (>= 0). Typical value = 0,55.
kdPUDemagnetizing factor, a function of exciter alternator reactances (<i>Kd</i>) (>= 0). Typical value = 1,1.
kdrPUVoltage regulator derivative gain (<i>Kdr</i>) (>= 0). Typical value = 10.
kePUExciter constant related to self-excited field (<i>Ke</i>). Typical value = 1.
kirPUVoltage regulator integral gain (<i>Kir</i>) (>= 0). Typical value = 5.
kprPUVoltage regulator proportional gain (<i>Kpr</i>) (> 0 if ExcAC8B.kir = 0). Typical value = 80.
ksPUCoefficient to allow different usage of the model-speed coefficient (<i>Ks</i>). Typical value = 0.
pidlimBooleanPID limiter indicator.
true = input limiter <i>Vpidmax</i> and <i>Vpidmin</i> is considered
false = input limiter <i>Vpidmax</i> and <i>Vpidmin</i> is not considered.
Typical value = true.
seve1FloatExciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>1</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>1</sub></i><i>]</i>) (>= 0). Typical value = 0,3.
seve2FloatExciter saturation function value at the corresponding exciter voltage, <i>Ve</i><i><sub>2</sub></i>, back of commutating reactance (<i>Se[Ve</i><i><sub>2</sub></i><i>]</i>) (>= 0). Typical value = 3.
taSecondsVoltage regulator time constant (<i>Ta</i>) (>= 0). Typical value = 0.
tdrSecondsLag time constant (<i>Tdr</i>) (> 0 if ExcAC8B.kdr > 0). Typical value = 0,1.
teSecondsExciter time constant, integration rate associated with exciter control (<i>Te</i>) (> 0). Typical value = 1,2.
telimBooleanSelector for the limiter on the block (<i>1/sTe</i>).
See diagram for meaning of true and false.
Typical value = false.
ve1PUExciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>1</sub></i>) (> 0). Typical value = 6,5.
ve2PUExciter alternator output voltages back of commutating reactance at which saturation is defined (<i>Ve</i><i><sub>2</sub></i>) (> 0). Typical value = 9.
veminPUMinimum exciter voltage output (<i>Vemin</i>) (<= 0). Typical value = 0.
vfemaxPUExciter field current limit reference (<i>Vfemax</i>). Typical value = 6.
vimaxPUInput signal maximum (<i>Vimax</i>) (> ExcAC8B.vimin). Typical value = 35.
viminPUInput signal minimum (<i>Vimin</i>) (< ExcAC8B.vimax). Typical value = -10.
vpidmaxPUPID maximum controller output (<i>Vpidmax</i>) (> ExcAC8B.vpidmin). Typical value = 35.
vpidminPUPID minimum controller output (<i>Vpidmin</i>) (< ExcAC8B.vpidmax). Typical value = -10.
vrmaxPUMaximum voltage regulator output (<i>Vrmax</i>) (> 0). Typical value = 35.
vrminPUMinimum voltage regulator output (<i>Vrmin</i>) (< 0). Typical value = 0.
vtmultBooleanMultiply by generator's terminal voltage indicator.
true =the limits <i>Vrmax</i> and <i>Vrmin</i> are multiplied by the generator’s terminal voltage to represent a thyristor power stage fed from the generator terminals
false = limits are not multiplied by generator's terminal voltage.
Typical value = false.