ExcELIN1
Class Description
Static PI transformer fed excitation system ELIN (VATECH) - simplified model. This model represents an all-static excitation system. A PI voltage controller establishes a desired field current set point for a proportional current controller. The integrator of the PI controller has a follow-up input to match its signal to the present field current. A power system stabilizer with power input is included in the model.
Attributes
Name | Type | Description |
---|---|---|
dpnf | PU | Controller follow up deadband (<i>Dpnf</i>). Typical value = 0. |
efmax | PU | Maximum open circuit excitation voltage (<i>Efmax</i>) (> ExcELIN1.efmin). Typical value = 5. |
efmin | PU | Minimum open circuit excitation voltage (<i>Efmin</i>) (< ExcELIN1.efmax). Typical value = -5. |
ks1 | PU | Stabilizer gain 1 (<i>Ks1</i>). Typical value = 0. |
ks2 | PU | Stabilizer gain 2 (<i>Ks2</i>). Typical value = 0. |
smax | PU | Stabilizer limit output (<i>smax</i>). Typical value = 0,1. |
tfi | Seconds | Current transducer time constant (<i>Tfi</i>) (>= 0). Typical value = 0. |
tnu | Seconds | Controller reset time constant (<i>Tnu</i>) (>= 0). Typical value = 2. |
ts1 | Seconds | Stabilizer phase lag time constant (<i>Ts1</i>) (>= 0). Typical value = 1. |
ts2 | Seconds | Stabilizer filter time constant (<i>Ts2</i>) (>= 0). Typical value = 1. |
tsw | Seconds | Stabilizer parameters (<i>Tsw</i>) (>= 0). Typical value = 3. |
vpi | PU | Current controller gain (<i>Vpi</i>). Typical value = 12,45. |
vpnf | PU | Controller follow up gain (<i>Vpnf</i>). Typical value = 2. |
vpu | PU | Voltage controller proportional gain (<i>Vpu</i>). Typical value = 34,5. |
xe | PU | Excitation transformer effective reactance (<i>Xe</i>) (>= 0). <i>Xe</i> represents the regulation of the transformer/rectifier unit. Typical value = 0,06. |
Relationships
Ancestors
Descendents
No descendent classes
Associations
None