Static PI transformer fed excitation system ELIN (VATECH) - simplified model. This model represents an all-static excitation system. A PI voltage controller establishes a desired field current set point for a proportional current controller. The integrator of the PI controller has a follow-up input to match its signal to the present field current. A power system stabilizer with power input is included in the model.

Attributes

NameTypeDescription
dpnfPUController follow up deadband (<i>Dpnf</i>). Typical value = 0.
efmaxPUMaximum open circuit excitation voltage (<i>Efmax</i>) (> ExcELIN1.efmin). Typical value = 5.
efminPUMinimum open circuit excitation voltage (<i>Efmin</i>) (< ExcELIN1.efmax). Typical value = -5.
ks1PUStabilizer gain 1 (<i>Ks1</i>). Typical value = 0.
ks2PUStabilizer gain 2 (<i>Ks2</i>). Typical value = 0.
smaxPUStabilizer limit output (<i>smax</i>). Typical value = 0,1.
tfiSecondsCurrent transducer time constant (<i>Tfi</i>) (>= 0). Typical value = 0.
tnuSecondsController reset time constant (<i>Tnu</i>) (>= 0). Typical value = 2.
ts1SecondsStabilizer phase lag time constant (<i>Ts1</i>) (>= 0). Typical value = 1.
ts2SecondsStabilizer filter time constant (<i>Ts2</i>) (>= 0). Typical value = 1.
tswSecondsStabilizer parameters (<i>Tsw</i>) (>= 0). Typical value = 3.
vpiPUCurrent controller gain (<i>Vpi</i>). Typical value = 12,45.
vpnfPUController follow up gain (<i>Vpnf</i>). Typical value = 2.
vpuPUVoltage controller proportional gain (<i>Vpu</i>). Typical value = 34,5.
xePUExcitation transformer effective reactance (<i>Xe</i>) (>= 0). <i>Xe</i> represents the regulation of the transformer/rectifier unit. Typical value = 0,06.