TransformerEnd

Class Description

A conducting connection point of a power transformer. It corresponds to a physical transformer winding terminal. In earlier CIM versions, the TransformerWinding class served a similar purpose, but this class is more flexible because it associates to terminal but is not a specialization of ConductingEquipment.

Attributes

NameTypeDescription
bmagSatPerCentCore shunt magnetizing susceptance in the saturation region.
endNumberIntegerNumber for this transformer end, corresponding to the end's order in the power transformer vector group or phase angle clock number. Highest voltage winding should be 1. Each end within a power transformer should have a unique subsequent end number. Note the transformer end number need not match the terminal sequence number.
groundedBoolean(for Yn and Zn connections) True if the neutral is solidly grounded.
magBaseUVoltageThe reference voltage at which the magnetizing saturation measurements were made.
magSatFluxPerCentCore magnetizing saturation curve knee flux level.
rgroundResistance(for Yn and Zn connections) Resistance part of neutral impedance where 'grounded' is true.
xgroundReactance(for Yn and Zn connections) Reactive part of neutral impedance where 'grounded' is true.

Relationships

Ancestors

Descendents

Associations

Source ClassSource CardinalityTargetTarget CardinalitySource NameSource Assoc. DescriptionTarget NameTarget Assoc. Description
TransformerEnd1PhaseTapChanger0..1TransformerEndTransformer end to which this phase tap changer belongs.PhaseTapChangerPhase tap changer associated with this transformer end.
TransformerEnd0..*TransformerStarImpedance0..1TransformerEndAll transformer ends having this star impedance.StarImpedance(accurate for 2- or 3-winding transformers only) Pi-model impedances of this transformer end. By convention, for a two winding transformer, the full values of the transformer should be entered on the high voltage end (endNumber=1).
TransformerEnd1RatioTapChanger0..1TransformerEndTransformer end to which this ratio tap changer belongs.RatioTapChangerRatio tap changer associated with this transformer end.
TransformerEnd0..*BaseVoltage0..1TransformerEndsTransformer ends at the base voltage. This is essential for PU calculation.BaseVoltageBase voltage of the transformer end. This is essential for PU calculation.
TransformerEnd0..*Terminal0..1TransformerEndAll transformer ends connected at this terminal.TerminalTerminal of the power transformer to which this transformer end belongs.
TransformerEnd1..*TransformerMeshImpedance0..*ToTransformerEndAll transformer ends this mesh impedance is connected to.ToMeshImpedanceAll mesh impedances between this 'from' and other 'to' transformer ends.
TransformerEnd1TransformerMeshImpedance0..*FromTransformerEndFrom end this mesh impedance is connected to. It determines the voltage reference.FromMeshImpedanceAll mesh impedances between this 'to' and other 'from' transformer ends.
TransformerEnd0..*TransformerCoreAdmittance0..1TransformerEndAll transformer ends having this core admittance.CoreAdmittanceCore admittance of this transformer end, representing magnetising current and core losses. The full values of the transformer should be supplied for one transformer end only.
TransformerEnd1WindingInsulation0..*ToWindingToWindingInsulations
TransformerEnd1WindingInsulation0..*FromWindingFromWindingInsulations