Skip to main content

PowerElectronicsConnection

Class Description

A connection to the AC network for energy production or consumption that uses power electronics rather than rotating machines.

Attributes

NameTypeDescription
maxIFaultPUMaximum fault current this device will contribute, in per-unit of rated current, before the converter protection will trip or bypass.
maxQReactivePowerMaximum reactive power limit. This is the maximum (nameplate) limit for the unit.
minQReactivePowerMinimum reactive power limit for the unit. This is the minimum (nameplate) limit for the unit.
pActivePowerActive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.
qReactivePowerReactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.
rResistanceEquivalent resistance (RG) of generator. RG is considered for the calculation of all currents, except for the calculation of the peak current ip. Used for short circuit data exchange according to IEC 60909.
r0ResistanceZero sequence resistance of the synchronous machine.
ratedSApparentPowerNameplate apparent power rating for the unit.
The attribute shall have a positive value.
ratedUVoltageRated voltage (nameplate data, Ur in IEC 60909-0). It is primarily used for short circuit data exchange according to IEC 60909.
The attribute shall be a positive value.
rnResistanceNegative sequence Thevenin resistance.
xReactancePositive sequence Thevenin reactance.
x0ReactanceZero sequence Thevenin reactance.
xnReactanceNegative sequence Thevenin reactance.

Relationships

Ancestors

Descendents

No descendent classes

Associations

Source ClassSource CardinalityTargetTarget CardinalitySource NameSource Assoc. DescriptionTarget NameTarget Assoc. Description
PowerElectronicsConnection1PowerElectronicsUnit0..*PowerElectronicsConnectionA power electronics unit has a connection to the AC network.PowerElectronicsUnitAn AC network connection may have several power electronics units connecting through it.
PowerElectronicsConnection1PowerElectronicsConnectionPhase0..*PowerElectronicsConnectionPower electronics connection of this power electronics connection phase.PowerElectronicsConnectionPhaseThe individual phases models for the power electronics connection.
PowerElectronicsConnection1WindTurbineType3or4Dynamics0..1PowerElectronicsConnectionThe power electronics connection associated with this wind turbine type 3 or type 4 dynamics model.WindTurbineType3or4DynamicsThe wind turbine type 3 or type 4 dynamics model associated with this power electronics connection.