ExternalNetworkInjection

Class Description

This class represents the external network and it is used for IEC 60909 calculations.

Attributes

NameTypeDescription
governorSCDActivePowerPerFrequencyPower Frequency Bias. This is the change in power injection divided by the change in frequency and negated. A positive value of the power frequency bias provides additional power injection upon a drop in frequency.
ikSecondBooleanIndicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik"). Used only if short circuit calculations are done according to superposition method.
maxInitialSymShCCurrentCurrentFlowMaximum initial symmetrical short-circuit currents (Ik" max) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909.
maxPActivePowerMaximum active power of the injection.
maxQReactivePowerMaximum reactive power limit. It is used for modelling of infeed for load flow exchange and not for short circuit modelling.
maxR0ToX0RatioFloatMaximum ratio of zero sequence resistance of Network Feeder to its zero sequence reactance (R(0)/X(0) max). Used for short circuit data exchange according to IEC 60909.
maxR1ToX1RatioFloatMaximum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) max). Used for short circuit data exchange according to IEC 60909.
maxZ0ToZ1RatioFloatMaximum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) max). Used for short circuit data exchange according to IEC 60909.
minInitialSymShCCurrentCurrentFlowMinimum initial symmetrical short-circuit currents (Ik" min) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909.
minPActivePowerMinimum active power of the injection.
minQReactivePowerMinimum reactive power limit. It is used for modelling of infeed for load flow exchange and not for short circuit modelling.
minR0ToX0RatioFloatIndicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik"). Used for short circuit data exchange according to IEC 6090.
minR1ToX1RatioFloatMinimum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) min). Used for short circuit data exchange according to IEC 60909.
minZ0ToZ1RatioFloatMinimum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) min). Used for short circuit data exchange according to IEC 60909.
pActivePowerActive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for steady state solutions.
qReactivePowerReactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for steady state solutions.
referencePriorityIntegerPriority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on.
voltageFactorPUVoltage factor in pu, which was used to calculate short-circuit current Ik" and power Sk". Used only if short circuit calculations are done according to superposition method.