WindContQIEC
Class Description
Q control model. Reference: IEC 61400-27-1:2015, 5.6.5.7.
Attributes
Name | Type | Description |
---|---|---|
iqh1 | PU | Maximum reactive current injection during dip (<i>i</i><i><sub>qh1</sub></i>). It is a type-dependent parameter. |
iqmax | PU | Maximum reactive current injection (<i>i</i><i><sub>qmax</sub></i>) (> WindContQIEC.iqmin). It is a type-dependent parameter. |
iqmin | PU | Minimum reactive current injection (<i>i</i><i><sub>qmin</sub></i>) (< WindContQIEC.iqmax). It is a type-dependent parameter. |
iqpost | PU | Post fault reactive current injection (<i>i</i><i><sub>qpost</sub></i>). It is a project-dependent parameter. |
kiq | PU | Reactive power PI controller integration gain (<i>K</i><i><sub>I,q</sub></i>). It is a type-dependent parameter. |
kiu | PU | Voltage PI controller integration gain (<i>K</i><i><sub>I,u</sub></i>). It is a type-dependent parameter. |
kpq | PU | Reactive power PI controller proportional gain (<i>K</i><i><sub>P,q</sub></i>). It is a type-dependent parameter. |
kpu | PU | Voltage PI controller proportional gain (<i>K</i><i><sub>P,u</sub></i>). It is a type-dependent parameter. |
kqv | PU | Voltage scaling factor for UVRT current (<i>K</i><i><sub>qv</sub></i>). It is a project-dependent parameter. |
rdroop | PU | Resistive component of voltage drop impedance (<i>r</i><i><sub>droop</sub></i>) (>= 0). It is a project-dependent parameter. |
tpfiltq | Seconds | Power measurement filter time constant (<i>T</i><i><sub>pfiltq</sub></i>) (>= 0). It is a type-dependent parameter. |
tpost | Seconds | Length of time period where post fault reactive power is injected (<i>T</i><i><sub>post</sub></i>) (>= 0). It is a project-dependent parameter. |
tqord | Seconds | Time constant in reactive power order lag (<i>T</i><i><sub>qord</sub></i>) (>= 0). It is a type-dependent parameter. |
tufiltq | Seconds | Voltage measurement filter time constant (<i>T</i><i><sub>ufiltq</sub></i>) (>= 0). It is a type-dependent parameter. |
udb1 | PU | Voltage deadband lower limit (<i>u</i><i><sub>db1</sub></i>). It is a type-dependent parameter. |
udb2 | PU | Voltage deadband upper limit (<i>u</i><i><sub>db2</sub></i>). It is a type-dependent parameter. |
umax | PU | Maximum voltage in voltage PI controller integral term (<i>u</i><i><sub>max</sub></i>) (> WindContQIEC.umin). It is a type-dependent parameter. |
umin | PU | Minimum voltage in voltage PI controller integral term (<i>u</i><i><sub>min</sub></i>) (< WindContQIEC.umax). It is a type-dependent parameter. |
uqdip | PU | Voltage threshold for UVRT detection in Q control (<i>u</i><i><sub>qdip</sub></i>). It is a type-dependent parameter. |
uref0 | PU | User-defined bias in voltage reference (<i>u</i><i><sub>ref0</sub></i>). It is a case-dependent parameter. |
windQcontrolModesType | WindQcontrolModeKind | Types of general wind turbine Q control modes (<i>M</i><i><sub>qG</sub></i>). It is a project-dependent parameter. |
windUVRTQcontrolModesType | WindUVRTQcontrolModeKind | Types of UVRT Q control modes (<i>M</i><i><sub>qUVRT</sub></i>). It is a project-dependent parameter. |
xdroop | PU | Inductive component of voltage drop impedance (<i>x</i><i><sub>droop</sub></i>) (>= 0). It is a project-dependent parameter. |
Relationships
Ancestors
Descendents
No descendent classes
Associations
Source Class | Source Cardinality | Target | Target Cardinality | Source Name | Source Assoc. Description | Target Name | Target Assoc. Description |
---|---|---|---|---|---|---|---|
WindContQIEC | 1 | WindTurbineType3or4IEC | 1 | WIndContQIEC | Wind control Q model associated with this wind turbine type 3 or type 4 model. | WindTurbineType3or4IEC | Wind turbine type 3 or type 4 model with which this reactive control model is associated. |