Skip to main content

WindContQIEC

Class Description

Q control model. Reference: IEC 61400-27-1:2015, 5.6.5.7.

Attributes

NameTypeDescription
iqh1PUMaximum reactive current injection during dip (<i>i</i><i><sub>qh1</sub></i>). It is a type-dependent parameter.
iqmaxPUMaximum reactive current injection (<i>i</i><i><sub>qmax</sub></i>) (> WindContQIEC.iqmin). It is a type-dependent parameter.
iqminPUMinimum reactive current injection (<i>i</i><i><sub>qmin</sub></i>) (< WindContQIEC.iqmax). It is a type-dependent parameter.
iqpostPUPost fault reactive current injection (<i>i</i><i><sub>qpost</sub></i>). It is a project-dependent parameter.
kiqPUReactive power PI controller integration gain (<i>K</i><i><sub>I,q</sub></i>). It is a type-dependent parameter.
kiuPUVoltage PI controller integration gain (<i>K</i><i><sub>I,u</sub></i>). It is a type-dependent parameter.
kpqPUReactive power PI controller proportional gain (<i>K</i><i><sub>P,q</sub></i>). It is a type-dependent parameter.
kpuPUVoltage PI controller proportional gain (<i>K</i><i><sub>P,u</sub></i>). It is a type-dependent parameter.
kqvPUVoltage scaling factor for UVRT current (<i>K</i><i><sub>qv</sub></i>). It is a project-dependent parameter.
rdroopPUResistive component of voltage drop impedance (<i>r</i><i><sub>droop</sub></i>) (>= 0). It is a project-dependent parameter.
tpfiltqSecondsPower measurement filter time constant (<i>T</i><i><sub>pfiltq</sub></i>) (>= 0). It is a type-dependent parameter.
tpostSecondsLength of time period where post fault reactive power is injected (<i>T</i><i><sub>post</sub></i>) (>= 0). It is a project-dependent parameter.
tqordSecondsTime constant in reactive power order lag (<i>T</i><i><sub>qord</sub></i>) (>= 0). It is a type-dependent parameter.
tufiltqSecondsVoltage measurement filter time constant (<i>T</i><i><sub>ufiltq</sub></i>) (>= 0). It is a type-dependent parameter.
udb1PUVoltage deadband lower limit (<i>u</i><i><sub>db1</sub></i>). It is a type-dependent parameter.
udb2PUVoltage deadband upper limit (<i>u</i><i><sub>db2</sub></i>). It is a type-dependent parameter.
umaxPUMaximum voltage in voltage PI controller integral term (<i>u</i><i><sub>max</sub></i>) (> WindContQIEC.umin). It is a type-dependent parameter.
uminPUMinimum voltage in voltage PI controller integral term (<i>u</i><i><sub>min</sub></i>) (< WindContQIEC.umax). It is a type-dependent parameter.
uqdipPUVoltage threshold for UVRT detection in Q control (<i>u</i><i><sub>qdip</sub></i>). It is a type-dependent parameter.
uref0PUUser-defined bias in voltage reference (<i>u</i><i><sub>ref0</sub></i>). It is a case-dependent parameter.
windQcontrolModesTypeWindQcontrolModeKindTypes of general wind turbine Q control modes (<i>M</i><i><sub>qG</sub></i>). It is a project-dependent parameter.
windUVRTQcontrolModesTypeWindUVRTQcontrolModeKindTypes of UVRT Q control modes (<i>M</i><i><sub>qUVRT</sub></i>). It is a project-dependent parameter.
xdroopPUInductive component of voltage drop impedance (<i>x</i><i><sub>droop</sub></i>) (>= 0). It is a project-dependent parameter.

Relationships

Ancestors

Descendents

No descendent classes

Associations

Source ClassSource CardinalityTargetTarget CardinalitySource NameSource Assoc. DescriptionTarget NameTarget Assoc. Description
WindContQIEC1WindTurbineType3or4IEC1WIndContQIECWind control Q model associated with this wind turbine type 3 or type 4 model.WindTurbineType3or4IECWind turbine type 3 or type 4 model with which this reactive control model is associated.