Skip to main content

PssSH

Class Description​

Siemens<sup>TM</sup> “H infinity” power system stabilizer with generator electrical power input. [Footnote: Siemens "H infinity" power system stabilizers are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]

Attributes​

NameTypeDescription
kPUMain gain (<i>K</i>). Typical value = 1.
k0PUGain 0 (<i>K0</i>). Typical value = 0,012.
k1PUGain 1 (<i>K1</i>). Typical value = 0,488.
k2PUGain 2 (<i>K2</i>). Typical value = 0,064.
k3PUGain 3 (<i>K3</i>). Typical value = 0,224.
k4PUGain 4 (<i>K4</i>). Typical value = 0,1.
t1SecondsTime constant 1 (<i>T1</i>) (> 0). Typical value = 0,076.
t2SecondsTime constant 2 (<i>T2</i>) (> 0). Typical value = 0,086.
t3SecondsTime constant 3 (<i>T3</i>) (> 0). Typical value = 1,068.
t4SecondsTime constant 4 (<i>T4</i>) (> 0). Typical value = 1,913.
tdSecondsInput time constant (<i>T</i><i><sub>d</sub></i>) (>= 0). Typical value = 10.
vsmaxPUOutput maximum limit (<i>Vsmax</i>) (> PssSH.vsmin). Typical value = 0,1.
vsminPUOutput minimum limit (<i>Vsmin</i>) (< PssSH.vsmax). Typical value = -0,1.

Relationships​

Ancestors​

Descendents​

No descendent classes

Associations​

None