OverexcLimX2

Class Description​

Field voltage or current overexcitation limiter designed to protect the generator field of an AC machine with automatic excitation control from overheating due to prolonged overexcitation.

Attributes​

NameTypeDescription
efd1PULow voltage or current point on the inverse time characteristic (<i>EFD</i><i><sub>1</sub></i>). Typical value = 1,1.
efd2PUMid voltage or current point on the inverse time characteristic (<i>EFD</i><i><sub>2</sub></i>). Typical value = 1,2.
efd3PUHigh voltage or current point on the inverse time characteristic (<i>EFD</i><i><sub>3</sub></i>). Typical value = 1,5.
efddesPUDesired field voltage if <i>m</i> = false or desired field current if <i>m </i>= true (<i>EFD</i><i><sub>DES</sub></i>). Typical value = 1.
efdratedPURated field voltage if m = false or rated field current if m = true (<i>EFD</i><i><sub>RATED</sub></i>). Typical value = 1,05.
kmxPUGain (<i>K</i><i><sub>MX</sub></i>). Typical value = 0,002.
mBoolean(<i>m</i>).
true = IFD limiting
false = EFD limiting.
t1SecondsTime to trip the exciter at the low voltage or current point on the inverse time characteristic (<i>TIME</i><i><sub>1</sub></i>) (>= 0). Typical value = 120.
t2SecondsTime to trip the exciter at the mid voltage or current point on the inverse time characteristic (<i>TIME</i><i><sub>2</sub></i>) (>= 0). Typical value = 40.
t3SecondsTime to trip the exciter at the high voltage or current point on the inverse time characteristic (<i>TIME</i><i><sub>3</sub></i>) (>= 0). Typical value = 15.
vlowPULow voltage limit (<i>V</i><i><sub>LOW</sub></i>) (> 0).