Skip to main content

OverexcLimIEEE

Class Description

The over excitation limiter model is intended to represent the significant features of OELs necessary for some large-scale system studies. It is the result of a pragmatic approach to obtain a model that can be widely applied with attainable data from generator owners. An attempt to include all variations in the functionality of OELs and duplicate how they interact with the rest of the excitation systems would likely result in a level of application insufficient for the studies for which they are intended. Reference: IEEE OEL 421.5-2005, 9.

Attributes

NameTypeDescription
hystPUOEL pickup/drop-out hysteresis (<i>HYST</i>). Typical value = 0,03.
ifdlimPUOEL timed field current limit (<i>I</i><i><sub>FDLIM</sub></i>). Typical value = 1,05.
ifdmaxPUOEL instantaneous field current limit (<i>I</i><i><sub>FDMAX</sub></i>). Typical value = 1,5.
itfpuPUOEL timed field current limiter pickup level (<i>I</i><i><sub>TFPU</sub></i>). Typical value = 1,05.
kcdPUOEL cooldown gain (<i>K</i><i><sub>CD</sub></i>). Typical value = 1.
krampFloatOEL ramped limit rate (<i>K</i><i><sub>RAMP</sub></i>). Unit = PU / s. Typical value = 10.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None