DERControlType
Class Description
Control modes supported by the DER. Bit positions SHALL be defined as follows:
0 - Charge mode
1 - Discharge mode
2 - opModConnect (Connect / Disconnect - implies galvanic isolation)
3 - opModEnergize (Energize / De-Energize)
4 - opModFixedPFAbsorbW (Fixed Power Factor Setpoint when absorbing active power)
5 - opModFixedPFInjectW (Fixed Power Factor Setpoint when injecting active power)
6 - opModFixedVar (Reactive Power Setpoint)
7 - opModFixedW (Charge / Discharge Setpoint)
8 - opModFreqDroop (Frequency-Watt Parameterized Mode)
9 - opModFreqWatt (Frequency-Watt Curve Mode)
10 - opModHFRTMayTrip (High Frequency Ride Through, May Trip Mode)
11 - opModHFRTMustTrip (High Frequency Ride Through, Must Trip Mode)
12 - opModHVRTMayTrip (High Voltage Ride Through, May Trip Mode)
13 - opModHVRTMomentaryCessation (High Voltage Ride Through, Momentary Cessation Mode)
14 - opModHVRTMustTrip (High Voltage Ride Through, Must Trip Mode)
15 - opModLFRTMayTrip (Low Frequency Ride Through, May Trip Mode)
16 - opModLFRTMustTrip (Low Frequency Ride Through, Must Trip Mode)
17 - opModLVRTMayTrip (Low Voltage Ride Through, May Trip Mode)
18 - opModLVRTMomentaryCessation (Low Voltage Ride Through, Momentary Cessation Mode)
19 - opModLVRTMustTrip (Low Voltage Ride Through, Must Trip Mode)
20 - opModMaxLimW (Maximum Active Power)
21 - opModTargetVar (Target Reactive Power)
22 - opModTargetW (Target Active Power)
23 - opModVoltVar (Volt-Var Mode)
24 - opModVoltWatt (Volt-Watt Mode)
25 - opModWattPF (Watt-PowerFactor Mode)
26 - opModWattVar (Watt-Var Mode)
All other values reserved.
Attributes
None
Relationships
Inherits from
Descendant classes
- No descendant classes
Associations
None