DERControlType

Class Description

Control modes supported by the DER. Bit positions SHALL be defined as follows:

0 - Charge mode

1 - Discharge mode

2 - opModConnect (Connect / Disconnect - implies galvanic isolation)

3 - opModEnergize (Energize / De-Energize)

4 - opModFixedPFAbsorbW (Fixed Power Factor Setpoint when absorbing active power)

5 - opModFixedPFInjectW (Fixed Power Factor Setpoint when injecting active power)

6 - opModFixedVar (Reactive Power Setpoint)

7 - opModFixedW (Charge / Discharge Setpoint)

8 - opModFreqDroop (Frequency-Watt Parameterized Mode)

9 - opModFreqWatt (Frequency-Watt Curve Mode)

10 - opModHFRTMayTrip (High Frequency Ride Through, May Trip Mode)

11 - opModHFRTMustTrip (High Frequency Ride Through, Must Trip Mode)

12 - opModHVRTMayTrip (High Voltage Ride Through, May Trip Mode)

13 - opModHVRTMomentaryCessation (High Voltage Ride Through, Momentary Cessation Mode)

14 - opModHVRTMustTrip (High Voltage Ride Through, Must Trip Mode)

15 - opModLFRTMayTrip (Low Frequency Ride Through, May Trip Mode)

16 - opModLFRTMustTrip (Low Frequency Ride Through, Must Trip Mode)

17 - opModLVRTMayTrip (Low Voltage Ride Through, May Trip Mode)

18 - opModLVRTMomentaryCessation (Low Voltage Ride Through, Momentary Cessation Mode)

19 - opModLVRTMustTrip (Low Voltage Ride Through, Must Trip Mode)

20 - opModMaxLimW (Maximum Active Power)

21 - opModTargetVar (Target Reactive Power)

22 - opModTargetW (Target Active Power)

23 - opModVoltVar (Volt-Var Mode)

24 - opModVoltWatt (Volt-Watt Mode)

25 - opModWattPF (Watt-PowerFactor Mode)

26 - opModWattVar (Watt-Var Mode)

All other values reserved.