DERAvailability
Class Description
Indicates current reserve generation status
Attributes
| Name | Type | Description |
|---|---|---|
| availabilityDuration | UInt32 | Indicates number of seconds the DER will be able to deliver active power at the reservePercent level. |
| reservePercent | PerCent | Percent of continuous delivered active power (%setMaxW) that is estimated to be available in reserve. |
| statVarAvail | ReactivePower | Estimated reserve reactive power, in var. Represents the lesser of received or delivered reactive power. |
| statWAvail | ActivePower | Estimated reserve active power, in watts. |
| readingTime | TimeType | The timestamp when the DER availability was last updated. |
| maxChargeDuration | UInt32 | Indicates number of seconds the DER will be able to receive active power at the reserveChargePercent level. |
| reserveChargePercent | PerCent | Percent of continuous received active power (%setMaxChargeRateW) that is estimated to be available in reserve. |
Relationships
Inherits from
Descendant classes
- No descendant classes
Associations