PFVArType1IEEEVArController
Class Description
IEEE VAR controller type 1 which operates by moving the voltage reference directly. Reference: IEEE 421.5-2005, 11.3.
Attributes
Name | Type | Description |
---|---|---|
tvarc | Seconds | Var controller time delay (<i>T</i><i><sub>VARC</sub></i>) (>= 0). Typical value = 5. |
vvar | PU | Synchronous machine power factor (<i>V</i><i><sub>VAR</sub></i>). |
vvarcbw | Float | Var controller deadband (<i>V</i><i><sub>VARC_BW</sub></i>). Typical value = 0,02. |
vvarref | PU | Var controller reference (<i>V</i><i><sub>VARREF</sub></i>). |
vvtmax | PU | Maximum machine terminal voltage needed for pf/VAr controller to be enabled (<i>V</i><i><sub>VTMAX</sub></i>) (> PVFArType1IEEEVArController.vvtmin). |
vvtmin | PU | Minimum machine terminal voltage needed to enable pf/var controller (<i>V</i><i><sub>VTMIN</sub></i>) (< PVFArType1IEEEVArController.vvtmax). |
Relationships
Ancestors
Descendents
No descendent classes
Associations
None