Skip to main content

LoadComposite

Class Description​

Combined static load and induction motor load effects. The dynamics of the motor are simplified by linearizing the induction machine equations.

Attributes​

NameTypeDescription
epfdFloatActive load-frequency dependence index (dynamic) (<i>Epfd</i>). Typical value = 1,5.
epfsFloatActive load-frequency dependence index (static) (<i>Epfs</i>). Typical value = 1,5.
epvdFloatActive load-voltage dependence index (dynamic) (<i>Epvd</i>). Typical value = 0,7.
epvsFloatActive load-voltage dependence index (static) (<i>Epvs</i>). Typical value = 0,7.
eqfdFloatReactive load-frequency dependence index (dynamic) (<i>Eqfd</i>). Typical value = 0.
eqfsFloatReactive load-frequency dependence index (static) (<i>Eqfs</i>). Typical value = 0.
eqvdFloatReactive load-voltage dependence index (dynamic) (<i>Eqvd</i>). Typical value = 2.
eqvsFloatReactive load-voltage dependence index (static) (<i>Eqvs</i>). Typical value = 2.
hSecondsInertia constant (<i>H</i>) (>= 0). Typical value = 2,5.
lfacFloatLoading factor (<i>L</i><i><sub>fac</sub></i>). The ratio of initial <i>P</i> to motor MVA base. Typical value = 0,8.
pfracFloatFraction of constant-power load to be represented by this motor model (<i>P</i><i><sub>FRAC</sub></i>) (>= 0,0 and <= 1,0). Typical value = 0,5.

Relationships​

Ancestors​

Descendents​

No descendent classes

Associations​

None