Skip to main content

ICCPVirtualControlCentre

Class Description

This contains the information that a particular actor exposes for a particular agreed upon ICCP Bilateral Table.

Attributes

NameTypeDescription
applicationSecurityRequirementApplicationSecurityKindSpecifies the expected security mechanism, per IEC 62351-4, to be utilized.
callingBooleanUsed to indicate if the Provider is responsible for initiating the TASE.2 connection. If the value is TRUE, the provider is responsible for establishing the association. If the value is FALSE, the peer provider of the Bilateral Table will need to establish the association.
clientAndServerBooleanIf True the value indicates that the entity represented by the bilateral table is capable of issuing requests and responding to request (e.g. bidirectional support of ICCP requests).

If False, this indicates that a calling entity (e.g. calling = True) will not be able to respond to ICCP requests. If False, and calling=False, this indicates that the entity will only respond to ICCP requests and not issue ICCP requests.
minimumUpdateIntervalIntegerSpecifies the fastest update interval that can be provided for integrity information and Transfer Set creation. The value is in seconds.
nameOfLocalICCStringSpecifies the ICC scope name that the remote can use to access the information in the Bilateral Table if the information is not VCC scoped. This value may not be null.
supportForBlock1BooleanPer IEC 60870-6-702: If true indicates support for basic services. Must always be true.
supportForBlock2BooleanPer IEC 60870-6-702: If true indicates support for extended conditions.
supportForBlock3BooleanPer IEC 60870-6-702: If true indicates support for blocked transfers.
supportForBlock4BooleanPer IEC 60870-6-702: If true indicates support for information messages.
supportForBlock5BooleanPer IEC 60870-6-702: If true indicates support for device control.
supportForDepriciatedBlock8BooleanPer IEC 60870-6-702: If true indicates support for accounts. The use of this block was deprecated in Edition 3.
transportSecurityRequirementBooleanIf true, then transport level security as specified by IEC 62351-6 is required.

Relationships

Ancestors

Descendents

No descendent classes

Associations

None